ABB  TRANSFER AND CHANGE-OVER SWITCHES                                             45




          —
          Manual change-over switches

          Technical data for UL/CSA switches OT30...100_C, OT200...800U_C



          Switch size                                       OT30_  OT60_   OT100_  OT200U_  OT400U_  OT600U_  OT800U_
          Data according to UL and CSA
          Standards                                         UL98   UL98    UL98   UL98    UL98   UL98   UL98
                                                            CSA 22.2#4 CSA 22.2#4 CSA 22.2#4 CSA 22.2#4 CSA 22.2#4 CSA 22.2#4 CSA 22.2#4  02
          General use ratings, 1- or 3-phase ratings   V A  600    600     600    600     600    600    600
                                                            30     60      100    200     400    600    800
          Horsepower, 3-phase ratings         240V     HP   10     20      30     75      125    200    250
                                              480V     HP   20     40      50     150     250    450    500
                                              600V     HP   30     40      50     200     350    500    500
          Short-circuit ratings  Required protection  Circuit   kA  -  -   -      14      25     35     42
                                              breaker
                                              Class J/L fuse kA  50 / -  50 / -  50 / -  65/100  100  100  100
                                              …fuse size  A  60    150     150    400/200  600   800    800
                                              Class RK5   kA  -    -       -      -       -      100    -
                                              fuse
                                              …fuse size  A  -     -       -      -       -      600    -
          Data according to IEC 60947-3
          Rated insulation voltage and rated  Pollution degree 3  V  750  750  750  1 000  1 000  1 000  1 000
          operational voltage AC20/DC20
          Dielectric strength  50 Hz 1min.             kV   6      6       6      10      10     10     10
          Rated impulse withstand voltage              kV   8      8       8      12      12     12     12
          Rated thermal current and rated   / ambient 40°C   In open air   A  40  63  100  250  400  800  1600
          operational current AC20/DC20       Cu       AWG/ 14 - 4  14 - 4  8 - 1/0  120  240    2x240  2x500
          ..with minimum conductor cross               mm²
          section
          Rated operational current, AC-21A   up to 690 V  A  40   63      100    250     400    800    1 600
          Rated operational current, AC-22A   up to 500 V  A  40   63      100    250     400    800    1 600
                                              690 V    A    40     63      100    250     400    800    1 600
          Rated operational current, AC-23A   up to 500 V  A  40   63      60     250     400    800    1 250
                                              690 V    A    40     40      40     250     400    800    1 250
          Rated conditional short-circuit   I p (r.m.s.) : 100 kA, 500 V îc (peak)  kA  -  -  -  40.5  61.5  90  106
          current I p (r.m.s.) and  Max. OFA_ fuse size   gG/aM  A  -  -   -      315/315   500/450  800/800  1 250/1 250
          corresponding max. allowed
          cut-off current î c peak value  1)  I p (r.m.s.) : 80 kA, 690 V  îc (peak)  kA  -  -  -  40.5  59  83.5  -
                               Max. OFA_ fuse size   gG/aM  A  -   -       -      355/315  500/500  800/1 000  -
          Rated short-time withstand current Icw (r.m.s.)  690V, 1s  kA  2.5  2.5  2.5  8  15    20     50
          Rated short-circuit making capacity I cm (peak)  690V  kA  3.6  3.6  3.6  30    65     80     92
          Mechanical endurance  Number of operating cycles  2)  Cycles 6000  6000  6000  8 000  8 000  5 000  3 000
          Terminal bolt size   Metric thread diameter x length  mm  -  -   -      M8x25   M10x30  M12x40  M12x60
          Terminal tightening torque  Counter torque required  Nm  -  -    -      15...22  30...44  50...75  50...75
          Operating torque     3-pole switches         Nm   2      2       2      7       16     27     78
          Weight without accessories  3-pole switch    kg   0.90   0.90    0.90   2.8     5.0    13.1   34.8
                               4-pole switch           kg   1.18   1.18    1.18   3.5     6.1    15.9   43.3
          Data according to IEC 60947-6-1
          Class of equipment                                -      -       -      PC      PC     PC     PC
          Rated short-time withstand current Icw (r.m.s.)  690 V 0.1s  kA  -  -  -  15    25     38     50
          Rated operational current, AC-31B   up to 415 V  A  -    -       -      250     400    800    1 600
          Rated operational current, AC-33B   up to 415 V  A  -    -       -      250     400    800    1 000
          1)  The fuse in single-phase test according to IEC 60269
          2)  Operating cycle: O - I - O - II - O