ABB  TRANSFER AND CHANGE-OVER SWITCHES                                             73




          —
          Optional accessories for motorized change-over switches

          Ordering information and technical data for auxiliary contacts



                                    —
                                    Auxiliary contact blocks for OTM40…125F
                                    Snap-on mounting to the switch, IP20, max. 2 blocks/ side. Ith = 16 A, suitable for cable cross sections max. 2 x
                                    2.5 mm². Simultaneous action with the main contacts.
                                                                                                     Delivery Weight/
                                    Suitable     Contact  Installation                               batch  unit
                                    for switches  functions  side  Type        Order code            pcs  kg           03
                                    OT_16...125F_C  1NO  Right   OA1G10        1SCA022353R4970       10   0.03
          OA1G01                    OT_16...125F_C  1NC  Right   OA8G01        1SCA022744R2240       10   0.03
          OA7G10
                                    OT_16...125F_C  1NO  Left    OA7G10        1SCA022673R1140       10   0.03
                                    OT_16...125F_C  1NC  Left    OA1G01        1SCA022353R4890       10   0.03
                                    OT63...125F3C  1NO+1NC  Either  OA2G11  1)  1SCA022379R8100      10   0.03
                                    1)  Not mountable on 4-pole change-over switches



                                    —
                                    Auxiliary contact blocks for OTM160…3200
           1G
           A
          O
             1
          OA1G10 0                  Mounting on the right side of the switch: Max. 4 auxiliary contact blocks/switch (totally 8 blocks). Types _AU
          OA8G01
          O A8 G0 1                 have gold plated contacts for harsh environments and low operating voltages. Simultaneous action with the
                                    main contacts, IP20.
                                                                                                     Delivery Weight/
                                    Suitable     Contact  Installation                               batch  unit
                                    for switches  functions  side  Type        Order code            pcs  kg
                                    OT_160…3200_  1NO    Right   OA1G10        1SCA022353R4970       10   0.03
                                    OT_160…3200_  1NC    Right   OA3G01        1SCA022456R7410       10   0.03
                                    OT_160…3200_  1NO    Right   OA1G10AU      1SCA022436R7910       10   0.03
                                    OT_160…3200_  1NC    Right   OA3G01AU      1SCA022819R5260       10   0.03
                                    Auxiliary contacts
                                    Technical data for auxiliary contacts according to IEC 60947-5-1, for OA1G_, OA2G_, OA3G_, OA7G_, OA8G_
                                    AC15                             DC12                 DC13
             1
            G
          OA2G11 1                  Ue         Ie         Ue         Ie         P         Ie         P
          OA
            2
                                    V          A          V          A          W         A          W
                                    230        6          24         10         240       2          50
                                    400        4          72         4          290       0.8        60
                                    415        4          125        2          250       0.55       70
                                    690        2          250        0.55       140       0.27       70
                                    -          -          440        0.1        44        -          -


                                    Function tables
                                    Function table of OT160…3200, OT160...800_Y and OTM160…2500 auxiliary contacts / Switch I (max. 2+2)
                                    Handle position    Main contacts      OA1G10 NO          OA3G01 NC
                                    I                  closed             closed             open
                                    0                  open               open               closed
                                    II                 closed             open               closed
                                    Function table of OT160…3200, OT160...800_Y and OTM160…2500 auxiliary contacts / Switch II (max. 2+2)
                                    Handle position    Main contacts      OA1G10 NO          OA3G01 NC
                                    I                  closed             open               closed
                                    0                  open               open               closed
                                    II                 closed             closed             open
   68   69   70   71   72   73   74   75   76   77   78