Page 77 - Changeover switch
P. 77
ABB TRANSFER AND CHANGE-OVER SWITCHES 77
—
Optional accessories for motorized change-over switches
Technical data and dimensional drawings for dual power sources
Technical data for dual power source ODPSE230C
Dual power source ODPSE230C
Rated operational voltage U [V] 220…240 V AC +/- 20%
Rated frequency 50 / 60 Hz +/- 10%
Short-circuit protection device Max. MCB 4 A
Nominal output current In [A] 4 A
Startup time Max. 1.0 s (with 230 V AC) 03
Operating transfer time LN1 - LN2 or LN2 - LN1 Max. 0.5 s (with 230 V AC)
Cable size 0.2…2.5 mm²
Rated impulse withstand voltage, U imp 4 kV
Overvoltage category III
Pollution degree 3
Protection rating for the front panel IP20
Operating temperature – 25...+ 60 °C
Transportation and storage temperature – 40...+ 70 °C
Altitude Max. 2 000m
Technical data for new dual power source ODPS230 with ATS functionality
Dual power source ODPS230
Rated operational voltage U [V] 220…240 V AC, 50 / 60 Hz
Maximum voltage 288 V AC
Pick-up voltage ≥198 V AC
Drop-out voltage ≤154 V AC
Operating time 1 s ± 0.5 s
Nominal output current In [A] 3.15 A
Rated conditional short-circuit current, I p (r.m.s.) 50 kA
Internal fuse T / 3.15 A / H*
Fuse size 6.3 x 32 mm
Rated impulse withstand voltage, U imp 4 kV
Overvoltage category III
Pollution degree 3
Cable size Max. 6 mm²
Protection rating for the front panel IP20
Operating temperature – 25...+ 60 °C
Transportation and storage temperature – 40...+ 70 °C
Altitude Max. 2 000m
* The breaking capacity must be 50 kA to achieve 50 kA Ip (r.m.s.) rating
Dimensional drawings for dual power sources
ODPS230 ODPSE230C
32 52
mm
Ø4,5 2 1 X11
DIA 0,18
2 ODPS
1 X12
100
2 LN1 78
1 X13
90 LN2
4
45 100
90 43
S07294 27,4
50
90 35,3
64
130
Main dimensions (mm)