ABB  TRANSFER AND CHANGE-OVER SWITCHES                                             75




          —
          Optional accessories for motorized change-over switches

          Technical data and dimensional drawings for automatic control units



          Technical data for automatic control units OMD300/800
          OMD300
          Rated operational voltage U e                        208 V AC - 480 V AC +/- 20% + N
                                       Phase - Neutral         120 V AC - 277 V AC +/- 20%
          Rated frequency                                      50 / 60 Hz +/- 10%
          Voltage sensing precision                            5%
          Frequency sensing precision                          1%                                                      03
          Relay ratings:               X21, X22                12 A, AC1, 250 V / 12 A, DC1, 24 V
                                       X23, X24                8 A, AC1, 250 V / 8 A, DC1, 24 V
                                       X26, X27, X28           10 A, AC1, 250 V / 5 A, DC1, 24 V
          Rated impulse withstand voltage, U imp               6 kV
          Overvoltage category                                 III
          Pollution degree                                     2
          OMD800
          Rated operational voltage U e on 3 phase system      100 V AC - 480 V AC +/- 20%
                                       Phase - Neutral         57.7 V AC - 277 V AC +/- 20%
          Rated operational voltage U e on 1 phase system
          1)                                                   57.7 V AC - 277 V AC +/- 20%
          Rated frequency                                      50 / 60 Hz +/- 10%
          Voltage sensing precision                            1%
          Frequency sensing precision                          1%
          Relay ratings:               X21, X22, X24           12 A, AC1, 250 V / 12 A, DC1, 24 V
                                       X23                     8 A, AC1, 250 V / 8 A, DC1, 24 V
                                       X29                     5 A, AC1, 250 V / 6 A, DC1, 24 V
          Rated impulse withstand voltage, U imp               6 kV
          Overvoltage category                                 III
          Pollution degree                                     2
          AUX voltage (1)                                      24 V DC - 110 V DC (-10% to +15%)
          Protection rating for the front panel                IP40
          Operating temperature                                – 20...+ 60 °C
          Transportation and storage temperature               – 25...+ 80 °C
          Altitude                                             Max. 2000m
          Humidity
          With condensation                                    5 %...98 %
          Without condensation                                 5 %...90 %
          1)  If on 1 phase system the voltage level is between 57.7 – 109 V AC, AUX voltage supply must be used






          OMD300/800


                  96             170
                                                          A07267 / M00392/OMD_CONTROLLER   A
                      OMD
           144
                                           138
          150


                                                   90

















          Main dimensions (mm)
   70   71   72   73   74   75   76   77   78   79   80