Page 377 - ABB_Motor _Protection_and_Control_catalogue_20221216
P. 377

ABB  MOTOR PROTECTION AND CONTROL                                               3/301

          —

          Auxiliary contact blocks for AF116 ... AF2850 contactors
          Electrical durability




          Electrical durability for AC-15 utilization category                                                        03
          AC-15 utilization category according to IEC 60947-5-1 / EN 60947-5-1:
          •  making current: 10 x Ie with cos ϕ = 0.7 and Ue
          •  breaking current: Ie with cos ϕ = 0.4 and Ue.
          This curves represent the electrical durability of the add-on auxiliary contacts, in relation to the breaking current.
          The curves have been drawn for resistive and inductive loads up to 690 V, 40...60 Hz.



             30                                               •  AF116 ... AF2850 contactors auxiliary contacts
             20                                               •  2-pole CAL18 and CAL19 add-on auxiliary contacts
             10
                                                              Example:
              5 3 2                                           Breaking current = 1.2 A
           Million operating cycles  0.5 1                    On the opposite curve at intersection "O" 1.2 A the
            2.7
                                                              corresponding value for the electrical durability is approxi-
                                                              mately 2.7 millions operating cycles.
             0.3
             0.2
             0.1
               0.02  0.05  0.1  0.2  0.3  0.5  1 1.2  2  3  45 6  10
                                   Breaking current (A)