ABB  MOTOR PROTECTION AND CONTROL                                                2/31

          —
          MS132-T, MS132-KT

          Technical data                                                                                              02




          Main circuit – Utilization characteristics according to IEC/EN
          Type                              MS132-T / -KT
          Standards                         IEC/EN 60947–2, IEC/EN 60947-4-1, IEC/EN 60947-1
          Rated operational voltage Ue      690 V AC
          Rated frequency                   50/60 Hz
          Operational frequency             0 ... 400 Hz
          Trip class                        10
          Number of poles                   3
          Duty time                         100%
          Mechanical durability             100000 cycles
          Electrical durability             50000 cycles
          Rated impulse withstand voltage Uimp  6 kV
          Rated insulation voltage Ui       690 V
          Rated operational current Ie      See ordering details
          Rated instantaneous short-circuit current setting Ii  See ordering details
          Rated service short-circuit breaking capacity Ics  See table "Short-circuit breaking capacity and back-up fuses"
          Rated ultimate short-circuit breaking capacity Icu  See table "Short-circuit breaking capacity and back-up fuses"
          Suitable for use in IT networks   Yes



          Short-circuit breaking capacity and back-up fuses
          lcs  Rated service short-circuit breaking capacity
          lcu  Rated ultimate short-circuit breaking capacity
          Iq (Icc) Rated conditional short-circuit current
          -   No back-up fuse required, because short-circuit proof up to Icu (for Icu see table below)

          Type       230 V AC         400 V AC          440 V AC           500 V AC          690 V AC
                     Ics   Icu  gG, aM  Ics  Icu   gG, aM  Ics  Icu  gG, aM  Ics  Icu  gG, aM  Ics  Icu   gG, aM
                     kA    kA   A     kA     kA    A    kA     kA    A     kA    kA    A     kA     kA    A
          MS132-0.16(K)T  100  100  -   100  100   -    100    100   -     100   100   -     100    100   -
          MS132-0.25(K)T  100  100  -   100  100   -    100    100   -     100   100   -     100    100   -
          MS132-0.4(K)T  100  100  -   100   100   -    100    100   -     100   100   -     100    100   -
          MS132-0.63(K)T  100  100  -   100  100   -    100    100   -     100   100   -     100    100   -
          MS132-1.0(K)T  100  100  -   100   100   -    100    100   -     100   100   -     100    100   -
          MS132-1.6(K)T  100  100  -   100   100   -    100    100   -     100   100   -     100    100   -
          MS132-2.5(K)T  100  100  -   100   100   -    100    100   -     100   100   -     100    100   -
          MS132-4.0(K)T  100  100  -   100   100   -    30     30    35 (1)  20  20    35 (1)  3    3     35 (1)
          MS132-6.3(K)T  100  100  -   100   100   -    30     30    63 (1)  20  20    63 (1)  3    3     50 (1)
          MS132-10(K)T  100  100  -   100    100   -    30     30    100 (1)  20  20   100 (1)  3   3     50 (1)
          MS132-12T  100   100  -     100    100   -    30     30    100 (1)  20  20   100 (1)  3   3     63 (1)
          MS132-16(K)T  100  100  -   100    100   -    30     30    125 (1)  20  20   125 (1)  3   3     63 (1)
          MS132-20(K)T  100  100  -   100    100   -    30     30    125 (1)  20  20   125 (1)  3   3     80 (1)
          MS132-25(K)T  50  50  125 (1)  50  50    125 (1)  30  30   125 (1)  10  10   125 (1)  3   3     100 (1)
          (1) Maximum rated current of the back-up fuse for short circuit up to 100kA if Icc > Ics