          Technical data


          Main pole – Utilization characteristics according to UL/NEMA/CSA
          Contactor types           AC operated B6, VB6, VB6A             B7, VB7, VB7A
                                    DC operated BC6, VBC6, VBC6A          BC7, VBC7, VBC7A
          Standards                         UL/CSA 60947-1, UL/CSA 60947-4-1
          Maximum operational voltage       600 V
          UL/CSA general use rating         12 A / 300 V (2)              16 A / 600 V (2)
          UL/CSA maximum 1-phase motor rating                                                                         04
           Full load current          120 V AC 5.8 A                      13.8 A
                                      240 V AC 4.9 A                      10.0 A
           Horse power rating         120 V AC 0.25 hp                    0.75 hp
                                      240 V AC 0.5 hp                     1.5 hp
          UL/CSA maximum 3-phase motor rating
           Full load current (1)   200 / 208 V AC 4.8 / 4.6 A             7.8 / 10.6 A
                                    220-240 V AC 6.8 A                    9.6 A
                                    440-480 V AC 4.8 A                    7.6 A
                                    550-600 V AC 1.7 A                    6.1 A
           Horse power rating (1)  200 / 208 V AC 1 hp                    2 / 3 hp
                                    220-240 V AC 2 hp                     3 hp
                                    440-480 V AC 3 hp                     5 hp
                                    550-600 V AC 1 hp                     5 hp
          Resistive                300 V per pole 8 A                     8 A
          Heating
          Incandescent Lamps       300 V per pole 6 A                     6 A
          Fluorescent Lamps        300 V per pole 8.4 A                   8.4 A
          Short-circuit protection device for contactors
          without thermal overload relay - motor protection excluded
           High fault current           600 V 100 kA (3)
           Fuse rating                  600 V 40 A
           Fuse type                    600 V Class J
          (1)  For the corresponding kW/A or hp/A values of 1500 r.p.m, 50 Hz or 1800 r.p.m, 60 Hz, 3-phase motors, see "Motor rated operational powers and currents".
          (2) Versions equipped with soldering pin terminals: 8 A / 300 V for B6 series and 12 A / 600 V for B7 series
          (3) Versions equipped with flat and soldering pin terminals: 5 kA


          General technical data
          Contactor types           AC operated B6, VB6, VB6A             B7, VB7, VB7A
                                    DC operated BC6, VBC6, VBC6A          BC7, VBC7, VBC7A
          Rated insulation voltage Ui
           acc. to IEC/EN 60947-4-1         690 V
           acc. to UL/CSA 60947-4-1         600 V
          Rated impulse withstand voltage Uimp  6 kV
          Ambient air temperature, close to contactor
           Operation  Fitted with thermal overload relay  -25 ... +50 °C
                   Without thermal overload relay  -25 ... +55 °C
           Storage                          -40 ... +80 °C
          Climatic withstand                Acc. to IEC 60947-1 Annex Q
          Maximum operating altitude (without derating)  2000 m
          Mechanical durability             107 operating cycles
          Resistance to shock               Half-sine
           acc. to IEC/EN 60068-2-27        15 g / 11 ms
           acc. to IEC/EN 60947-1 Annex. Q  Category E
          Resistance to vibrations          Sinusoidal
           acc. to IEC/EN 60068-2-6         5 g / 3 ... 150 Hz
           acc. to IEC/EN 60947-1 Annex. Q  Category E