Page 723 - ABB_Motor _Protection_and_Control_catalogue_20221216
P. 723

ABB  MOTOR PROTECTION AND CONTROL                                                5/73

          —
          NS..S and NSL..S  contactor relays - with spring terminals

          Technical data




          Contact utilization characteristics according to IEC
          Contactor relay types         AC operated NS..S
                                       DC operated NSL..S
          Standards                            IEC 60947-5-1 and EN 60947-5-1
          Rated operational voltage Ue max.    690 V
          Rated frequency (without derating)   50 / 60 Hz
          Conventional free-air thermal current Ith θ ≤ 40 °C  10 A
          Ie / Rated operational current AC-15
          acc. to IEC 60947-5-1     24-127 V 50/60 Hz 6 A
                                    220-240 V 50/60 Hz 4 A
                                   400-440 V 50/60 Hz 3 A
                                      500 V 50/60 Hz 2 A                                                              05
                                      690 V 50/60 Hz 2 A
          Making capacity AC-15                10 x Ie AC-15 acc. to IEC 60947-5-1
          Breaking capacity AC-15              10 x Ie AC-15 acc. to IEC 60947-5-1
          Ie / Rated operational current DC-13
          acc. to IEC 60947-5-1           24 V DC 6 A / 144 W
                                          48 V DC 2.8 A / 134 W
                                          72 V DC 1 A / 72 W
                                          110 V DC 0.55 A / 60 W
                                          125 V DC 0.55 A / 69 W
                                         220 V DC 0.27 A / 60 W
                                         250 V DC 0.27 A / 68 W
          Short-circuit protection device for contactors
          Ue ≤ 500 V AC - gG type fuse         10 A
          Rated short-time withstand current Icw  for 1.0 s 100 A
          at 40 °C ambient temperature,in free air from    for 0.1 s 140 A
          a cold state
          Minimum switching capacity           12 V / 3 mA
          with failure rate acc. to IEC 60947-5-4  10-7
          Non-overlapping time between N.O. and N.C. contacts  1.5 ms
          Power dissipation per pole at 6 A    0.1 W
          Max. electrical switching frequency  AC-15 1200 cycles/h
                                           DC-13 900 cycles/h
          Mechanically linked contacts         Built-in N.O. or N.C. auxiliary contacts and additional N.O. or N.C. auxiliary contacts (CA3..S aux. contact blocks) are
          acc. to annex L of IEC 60947-5-1     mechanically linked contacts.

          Contact utilization characteristics according to UL / CSA
          Contactor relay types         AC operated NS..S
                                       DC operated NSL..S
          Standards                            UL 508, CSA C22.2 N°14
          Max. operational voltage             600 V AC, 250 V DC
          Pilot duty                           A600, Q300
           AC thermal rated current            10 A
           AC maximum volt-ampere making       7200 VA
           AC maximum volt-ampere breaking     720 VA
           DC thermal rated current            2.5 A
           DC maximum volt-ampere making-breaking  69 VA
   718   719   720   721   722   723   724   725   726   727   728