Page 725 - ABB_Motor _Protection_and_Control_catalogue_20221216
P. 725

ABB  MOTOR PROTECTION AND CONTROL                                                5/75

          —
          NS..S and NSL..S  contactor relays - with spring terminals

          Technical data




          General technical data
          Contactor relay types          AC operated NS..S
                                         DC operated NSL..S
          Rated insulation voltage Ui
            acc. to IEC 60947-5-1                690 V
            acc. to UL / CSA                     600 V
          Rated impulse withstand voltage Uimp.  6 kV
          Pollution degree                       3
          Ambient air temperature close to contactor relay
                      Operation in free air      -40...+70 °C
                      Storage                    -60...+80 °C
          Climatic withstand                     Category B according to IEC 60947-1 Annex Q                          05
          Maximum operating altitude (without derating)  3000 m
          Mechanical durability
            Number of operating cycles           20 millions operating cycles
            Max. switching frequency             3600 cycles/h
          Shock withstand                        1/2 sinusoidal shock for 11 ms: no change in contact position, closed or open position
          acc. to IEC 60068-2-27 and EN 60068-2-27  Shock direction
          Mounting position 1                    NS contactor relays - AC operated  NSL contactor relays - DC operated
                        C1                     A 20 g                           20 g closed position / 10 g open position
                                              B1 5 g                            15 g closed position / 5 g open position
          A      A  B1      B2
                                              B2 15 g                           10 g
                                              C1 19 g closed position / 8 g open position  19 g closed position / 8 g open position
                        C2
                                              C2 16 g closed position / 13 g open position  14 g closed position / 8 g open position
          Vibration withstand                    5...300 Hz
          acc. to IEC 60068-2-6                  3 g closed position / 2 g open position

          Connecting characteristics
          Contactor relay types          AC operated NS..S
                                         DC operated NSL..S
          Main terminals


                                                 Spring terminals
          Connection capacity (min. ... max.)
            Pole and coil terminals
                   Rigid Solid/Stranded       1 x 0.75...2.5 mm²
                                              2 x 0.75...2.5 mm²
                   Flexible with non insulated ferrule  1 x 0.75...2.5 mm²
                                              2 x 0.75...2.5 mm²
                   Flexible with insulated ferrule  1 x 0.75...1.5 mm²
                                              2 x 0.75...1.5 mm²
            Connection capacity acc. to UL / CSA  1 or 2 x AWG 18...14
            Stripping length                     10 mm
          Degree of protection
          acc. to IEC 60947-1 / EN 60947-1 and IEC 60529 / EN 60529
            All terminals                        IP20
          Screwdriver type                       Flat Ø 3.5