5/74             ABB  MOTOR PROTECTION AND CONTROL

          —
          NS..S and NSL..S  contactor relays - with spring terminals

          Technical data




          Magnet system characteristics for NS..S contactor relays
          Contactor relay types          AC operated NS..S
          Coil operating limits           AC supply
          acc. to IEC 60947-5-1                  0.85...1.1 x Uc (at θ ≤ 60 °C); Uc (at θ ≤ 70 °C)
          AC control voltage  Rated control circuit voltage Uc  at 50 Hz 24...415 V
                                           at 60 Hz 24...415 V
                     Coil consumption Average pull-in value  50 Hz 33 VA
                                            60 Hz 33 VA
                                           50/60 Hz 33 VA
                               Average holding value  50 Hz 6.5 VA / 1.5 W
                                            60 Hz 5 VA / 1.2 W
                                           50/60 Hz 6.5 VA / 1.5 W
   05
          Drop-out voltage                       Approx. 30...50 % of Uc
          Operating time
            Between coil energization and:  N.O. contact closing 9...24 ms
                                    N.C. contact opening 6...18 ms
            Between coil de-energization and:  N.O. contact opening (1) 5...19 ms
                                   N.C. contact closing (1) 7...22 ms
                                                 (1) The use of RC5-1 surge suppressor increases opening time by a factor of 2 to 3.

          Magnet system characteristics for NSL..S contactor relays
          Contactor relay types          DC operated NSL..S
          Coil operating limits           DC supply
          acc. to IEC 60947-5-1                  0.85...1.1 x Uc (at θ ≤ 60 °C); Uc (at θ ≤ 70 °C)
          DC control voltage
            Rated control circuit voltage Uc     12...240 V DC
            Coil consumption  Average pull-in value  3 W
                        Average holding value    3 W
          Drop-out voltage                       Approx. 10...40 % of Uc
          Coil time constant  Open            L/R 12 ms
                        Closed                L/R 40 ms
          Operating time
            Between coil energization and:  N.O. contact closing 36...59 ms
                                    N.C. contact opening 31...53 ms
            Between coil de-energization and:  N.O. contact opening (1) 13...17 ms
                                   N.C. contact closing (1) 15...20 ms
                                                 (1) The use of RT5 surge suppressor increases opening time by a factor of 1.1 to 1.2.
          Mounting characteristics and conditions for use
          Contactor relay types          AC operated NS..S
                                         DC operated NSL..S
          Mounting positions                         Pos. 2

                                                 Pos. 4
                                                         Pos. 3

                                                       Pos. 1     Pos. 5


          Mounting distances                     The contactor relays can be assembled side by side.
          Fixing  On rail according to IEC 60715, EN 60715  35 x 7.5 mm or 35 x 15 mm
                  By screws (not supplied)       2 x M4 screws placed diagonally