6/36             ABB  MOTOR PROTECTION AND CONTROL

          —
          E16DU, EF19, EF45 electronic overload relays – 0.10 to 45.0 A

          Technical data




          Technical diagram – Intermittent periodic duty
          (Op/h)   Trip class 10E    (Op/h)  Trip class 20E    (Op/h)  Trip class 30E
                                                                50
               a
           160   t   = 0.5 s          80                        45   t   = 5 s
                                                                    a
                                          a
           140                        70                        40
                                         t   = 2 s
          switching frequency      100   t   = 1 s  switching frequency      50   t   = 4 s  switching frequency      30   t   = 10 s
           120
                                                                35
                                      60
               a
                                                                25
           80
                                      40
                                                                   a
                                           a
                                                                20
           60
                                      30
               a
               t   = 1.5 s
                                            a
           40
                                                                     a
                                         a
                                                                10
               a
              t   = 3 s               20   t   = 8 s t   = 6 s  15   t   = 15 s
                                        a
                                                                    a
           20                         10   t   = 10 s              t   = 20 s
               a
              t   = 5 s                  t   = 12 s             5   t   = 25 s
                                                                   a
                                         a
            0                   2CDC232001F0214  0        2CDC232002F0214           2CDC232003F0214
             0   20  40  60  80  100   (%)  0   20  40  60  80  100   (%)  0  0   20  40  60  80  100  (%)
                 duty ratio                duty ratio                duty ratio
          Trip class 10E            Trip class 20E            Trip class 30E
          Main circuit – Utilization characteristics according to UL/CSA
          Type                              E16DU               EF19                EF45
   06
          Standards                         UL 508, CSA 22.2 No. 14
          Maximum operational voltage       600 V AC
          Trip rating                       125% of FLA
          Full load amps (FLA)              See table "Full load amps and short-circuit protective device"
          Short-circuit rating RMS symmetrical  See table "Full load amps and short-circuit protective device"
          Short-circuit protective device   See table "Full load amps and short-circuit protective device"
          Auxiliary circuit according to UL/CSA
          Type                              E16DU               EF19                EF45
          Contact rating             N.C., 95-96 B600, Q300     B600, Q600
                                     N.O., 97-98 B600, Q300     B600, Q600
          Conventional free-air thermal current  5 A
          Full load amps and short-circuit protective device
          Type             Full load amps (FLA)  Short-circuit protective device
                                           480 V AC               600 V AC
                                           SCCR       Fuse type   SCCR       Fuse type   SCCR       Fuse type
          E16DU-0.32       0.32 A          50 kA      2 A, Class J  5 kA     2 A, K5 / RK5  100 kA  2 A, Class J
          E16DU-1.0        1.00 A          50 kA      2 A, K5 / RK5  5 kA    2 A, K5 / RK5  100 kA  2 A, Class J
          E16DU-2.7        2.70 A          50 kA      4 A, K5 / RK5  5 kA    4 A, K5 / RK5  100 kA  4 A, Class J
          E16DU-6.3        6.30 A          50 kA      15 A, K5 / RK5  5 kA   15 A, K5 / RK5  100 kA  15 A, Class J
          E16DU-18.9       18.90 A         50 kA      30 A, K5 / RK5  5 kA   30 A, K5 / RK5  100 kA  30 A, Class J
          Type             Full load amps (FLA)  Short-circuit protective device
                                           480 V AC               600 V AC
                                           SCCR       Fuse type   SCCR       Fuse type   SCCR       Fuse type
          EF19-0.32        0.32 A          50 kA      2 A, Class J  5 kA     2 A, K5 / RK5  100 kA  2 A, Class J
          EF19-1.0         1.00 A          50 kA      2 A, K5 / RK5  5 kA    2 A, K5 / RK5  100 kA  2 A, Class J
          EF19-2.7         2.70 A          50 kA      4 A, K5 / RK5  5 kA    4 A, K5 / RK5  100 kA  4 A, Class J
          EF19-6.3         6.30 A          50 kA      15 A, K5 / RK5  5 kA   15 A, K5 / RK5  100 kA  15 A, Class J
          EF19-18.9        18.90 A         50 kA      30 A, K5 / RK5  5 kA   30 A, K5 / RK5  100 kA  30 A, Class J
          Type             Full load amps (FLA)  Short-circuit protective device
                                           480 V AC               600 V AC
                                           SCCR       Fuse type   SCCR       Fuse type   SCCR       Fuse type
          EF45-30          30 A            18 kA      150 A, K5 / RK5  18 kA  150 A, K5 / RK5  100 kA  150 A, Class J
          EF45-45          45 A            18 kA      200 A, K5 / RK5  18 kA  200 A, K5 / RK5  100 kA  200 A, Class J