Page 783 - ABB_Motor _Protection_and_Control_catalogue_20221216
P. 783

ABB  MOTOR PROTECTION AND CONTROL                                                6/45

          —
          EF205, EF370 electronic overload relays – 63 to 380 A

          Technical data




          Main circuit – Utilization characteristics according to UL/CSA
          Type                              EF205, EF370
          Standards                         UL 508, CSA 22.2 No. 14, UL 60947-4-1A
          Maximum operational voltage       600 V AC
          Trip rating                       125% of FLA
          Full load amps (FLA)              See table "Full load amps and short-circuit protective device"
          Short-circuit rating RMS symmetrical  See table "Full load amps and short-circuit protective device"
          Short-circuit protective device   See table "Full load amps and short-circuit protective device"
          Auxiliary circuit according to UL/CSA
          Type                              EF205, EF370
          Contact rating             N.C., 95-96 B600, Q600
                                     N.O., 97-98 B600, Q600
          Conventional thermal current      6 A
          Full load amps and short-circuit protective device
          Type            Full load amps (FLA)  Short-circuit protective device
                                          480 V AC                600 V AC                                            06
                                          SCCR        Fuse type   SCCR       Fuse type   SCCR        Fuse type
          EF205-210       210 A           10 kA       400 A, R5/RK5  10kA    400 A, R5/RK5  100 kA   400 A, J
          EF370-380       380 A           18 kA       800 A, L/T  18kA       800 A, L/T  -           -