6/50             ABB  MOTOR PROTECTION AND CONTROL

          —
          EF460, EF750, EF1250DU electronic overload relays – 150 to 1250 A

          Technical data




          Main circuit – Utilization characteristics according to UL/CSA
          Type                              EF460                  EF750                 EF1250DU
          Standards                         UL60947-1, UL60947-4-1
          Maximum operational voltage       600 V AC
          Trip rating                       125% of FLA
          Auxiliary circuit according to UL/CSA
          Type                              EF460                  EF750                 EF1250DU
          Contact rating             N.C., 95-96 B600, Q600
                                     N.O., 97-98 B600, Q600
          Conventional thermal current      5 A

          General data
          Type                              EF460                  EF750                 EF1250DU
          Pollution degree                  3
          Phase loss sensitive              Yes
          Ambient air temperature
              Operation  Open - compensated  -25 ... +70 °C
   06
              Storage                       -50 ... +85 °C
          Ambient air temperature compensation  Acc. to IEC/EN60947-4-1
          Maximum operating altitude permissible  2000 m
          Resistance to shock acc. to IEC 60068-2-27  25g / 11 ms
          Resistance to vibrations acc. to IEC 60068-2-6  5g / 3 … 150 Hz
          Degree of protection  Housing     IP20
                       Main circuit terminals  IP00
          Electrical connection
          Auxiliary circuit
          Type                              EF460                  EF750                 EF1250DU
          Connecting capacity
                 Rigid                 1 or 2 x 1 ... 4 mm²
                 Flexible with ferrule  1 or 2 x 0.75 ... 2.5 mm²
                 Flexible with insulated ferrule  1 or 2 x 0.75 ... 2.5 mm²
                 Flexible              1 or 2 x 0.75 ... 2.5 mm²
                 Stranded acc. to UL/CSA  1 or 2 x AWG 18-10
                 Flexible acc. to UL/CSA  1 or 2 x AWG 18-10
          Stripping length                  9 mm
          Tightening torque                 0.8 ... 1.2 Nm / 7 ... 11 Ib.in
          Recommended screw driver          M3.5 (Pozidriv 2)