          Technical data



          Data at Ta = 25 °C and rated values, unless otherwise indicated

          Type                                                    CM-TCN.011             CM-TCN.012
          Input circuit                                           A1-A2
                                                                  24-240 V AC/DC*
          Rated control supply voltage U s
          Rated control supply voltage U s tolerance              -15 ... +10 %
          Rated frequency                                      AC  50 - 60 Hz
          Frequency range                                      AC  45 - 66 Hz
          Typical current consumption                    24 V AC/DC  typ. 30 mA / max. 40 mA
                                                           115 V AC  typ. 16 mA / max. 20 mA
                                                          230 V AC  typ. 13 mA / max. 15 mA
          Power failure buffering time                            min. 20 ms
          Measuring circuits                                      xT1, xT2, xT3
          Sensor type                                             PT100, PT1000**, PTC, NTC, bi-metal switch
          Connection of the sensor                          2-wire  yes, jumper xT2 - xT3
                                                            3-wire  yes, use terminal xT1, xT2, xT3
          Interrupted wire detection                              yes
          Short-circuit detection                                 yes                                                 08
          Measuring ranges                                  PT100  -200 °C … +850 °C / -328 °F ... +1562 °F
                                                           PT1000  -200 °C ... +850 °C / -328 °F ... +1562 °F**
                                                              NTC  +80 °C ... +155 °C / +176 °F ... +311 °F
                                                              PTC  max. total resistance of connected resistors in cold state <750 Ohm
          Monitoring functions                                    undertemperature, overtemperature, window monitoring
          Measuring input range                                   -200 … +850 °C / -328 … +1562 °F
          Hysteresis related to the threshold values              1 … 99.9 °C / 1.8 … 179.8 °F
          Measuring principle                                     continuous current
          Typical current in the sensor circuit             PT100  0.5 mA
                                                           PT1000  0.5 mA
          Maximum current in sensor circuit                       0.5 mA
          Measuring accuracy                                      ± 0.5 K (-50 ... +200 °C / -58 ... +392 °F)
                                                                  ± 1 K (< -50 °C / -58 °F and > 200 °C / 392 °F)
          Accuracy within the rated control supply voltage tolerance  < 0.05 % full scale/1 V
          Accuracy within the temperature range                   < 0.05 % full scale/1 K
          Repeat accuracy (constant parameters)                   ± 0.07 % full scale
          Maximum measuring cycle                                 < 2 s
          Maximum cable length                                    500 m / 1 mm  (shielded cable)
                                                                           2
          Control circuits
          Type of triggering                                      volt-free triggering
          Control function                                     S1  remote reset
          Maximum input current                                   < 1.5 mA
          Maximum no-load voltage at the control inputs           < 15 V
          Minimum control pulse length                            150 ms
          Maximum cable length at the control inputs              100 m - 100 pF/m
          * CM-TCN.011: supply voltage 24-240 V AC/DC for revision G or later and supply voltage 24 V AC/DC for revision F or earlier.
          ** When CM-TCN is used with PT1000 sensors, a bridge must be installed between terminals xT2 and xT3 of unused measuring circuits. The bridge must
          also be installed between open terminals xT2 and xT3 when CM-TCN is used with one or two PT1000 in combination with PTC or NTC or bimetal switch.