Page 816 - ABB_Motor _Protection_and_Control_catalogue_20221216
P. 816

8/10             ABB  MOTOR PROTECTION AND CONTROL




          —
          Smart monitoring relays

          Technical data





          Type                                                    CM-TCN.011             CM-TCN.012
          Timing functions
          Power-on delay                                          2-999.9 s
          ON-delay R1, R2, R3 *                                   0-6553.5 s
          OFF-delay R1, R2, R3 *                                  0-6553.5 s
          Cyclic switching function                        On time  1 min - 1 day
                                                          cycle time  10 min - 1 year
          Indication of operational states
          Control supply voltage applied                          LED green
          Cyclic switching function running                       LED orange
          Internal fault                                          LED red on
          Short circuit                                           LED red: Y
          Wire break                                              LED red: Z
          Overtemperature / Measurement value exceeds high limit     LED red: W
          Undertemperature / Measurement value exceeds low limit    LED red: X
          Parameter error                                         Orange and red LEDs alternate
   08
          NFC pairing                                             LED orange: W
          For details see the message on the display
          Display
          Technology                                              LCD
          Backlight                                            on  press button
                                                              off  switch-off delay adjustable, 10 s -1 h (default 10 s)
          Resolution                                              128 x 64 pixel
          Display size                                            25.58 x 12.78 mm
          Operating controls
          Push-rotate button                                      Operable with screw driver: PZ1
                                                                  DIN ISO 8764-1
          Near field communication (NFC)
          Standards                                               ISO/IEC 14443 Part 2+3
                                                                  NFC Forum Type 2 tag compliant
          Communication interface
          Communication protocol                                  -                      Modbus RTU
          Physical interface                                      -                      two-wire RS-485
          Integrated termination resistors                        -                      no
          Possible bus addresses                                  -                      1 ... 247
          Baud rates                                              -                      1200, 2400, 4800, 9600, 19200,
                                                                                         38400, 57600, 115200 B/s
          Typical response time                                   -                      < 30 ms
          Bus master supervision time / Timeout                   -                      adjustable 1 … 255 s in steps of 1 s
          Frame                                                   -                      8 data, Even, 1 stop
                                                                                         8 data, Odd, 1 stop
                                                                                         8 data, None, 2 stop
                                                                                         8 data, None, 1 stop
          * If the selected ON-delay or OFF-delay is less than 2 s, the maximum measuring cycle should be taken into account.