Page 818 - ABB_Motor _Protection_and_Control_catalogue_20221216
P. 818

8/12             ABB  MOTOR PROTECTION AND CONTROL




          —
          Smart monitoring relays

          Technical data



          Type                                                    CM-TCN.011             CM-TCN.012
          Environmental data
          Ambient temperature ranges                      operation  -25 °C...+60 °C (-13...+140 °F)
                                                           storage  -40 °C...+85 °C (-40...+185 °F)
          Damp heat, cyclic                        IEC/EN 60068-2-30  6 x 24 h cycle, 55 °C, 95 % RH
          Climatic class                            IEC/EN 60721-3-3  3K5 (no condensation, no ice formation)
          Vibration, sinusoidal                                   class 1
          Shock                                                   class 1
          Isolation data
          Rated impulse withstand voltage (U imp)   supply circuit / measuring circuit  6 kV
          EN/IEC60664-1                 and modbus / output circuits (relay)

                                         output circuit 1 / output circuit 2 /  4 kV
                                                      output circuit 3
          Rated insulation voltage U i Basic   supply circuit / measuring circuit  600 V
          insulation                    and modbus / output circuits (relay)

                                         output circuit 1 / output circuit 2 /  300 V
                                                      output circuit 3
          Protective separation IEC/EN 61140  supply circuit / measuring circuit  300 V
                                        and modbus / output circuits (relay)

                                         output circuit 1 / output circuit 2 /  150 V
   08
                                                      output circuit 3
          Pollution degree                                        3
          Overvoltage category                                    III
          Standards/Directives
          Standards                                               IEC/EN 60947-5-1
          Low Voltage Directive                                   2014/35/EU
          EMC Directive                                           2014/30/EU
          RoHS Directive                                          2011/65/EU incl. 2015/863/EU
          WEEE Directive                                          2012/19/EU
          RED Directive                                           2014/53/EU
          Electromagnetic compatibility
          Interference immunity to                                IEC/EN 60947-5-1
             electrostatic discharge                IEC/EN 61000-4-2  level 2, 4 kV contact discharge, 8 kV air discharge
             radiated, radio-frequency, electromagnetic field  IEC/EN 61000-4-3  level 3, 10 V/m
             electrical fast transient / burst      IEC/EN 61000-4-4  level 3 / 2 kV, 5 kHz
             surge                                  IEC/EN 61000-4-5  supply circuit: level 3; L-L 1 kV, L-PE 2 kV
                                                                  relay circuit: level 3; L-PE 2 kV
                                                                  measuring circuit, remote S1: level 2; L-PE 1 kV
             conducted disturbances, induced by     IEC/EN 61000-4-6  level 3, 10 V
             radio-frequency fields
             voltage dips, short interruptions     IEC/EN 61000-4-11  class 3
             and voltage variations
          Interference emission                                   IEC/EN 60947-5-1
             high-frequency radiated                              fulfilled (environment B)
             high-frequency conducted                             fulfilled (environment A and B)