Page 833 - ABB_Motor _Protection_and_Control_catalogue_20221216
P. 833

ABB  MOTOR PROTECTION AND CONTROL                                                10/7

          —
          DRAF09 … DRAF16 enclosed direct-on-line starters

          Up to 7.5 kW and 10 hp, protected by thermal overload relays
          AC operated


                                    Enclosed direct-on-line (DOL) starters are used for controlling 3-phase asynchronous motors up
                                    to 690 V AC.
                                    Each starter is delivered assembled and wired. It contains:
                                    •  IP66 and type 4X plastic enclosure with double insulation, equiped with:
                                        - 1 green flush "I" ON button and 1 red protruding "O" OFF/RESET button
                                        - 4 cable inlets and outlets via knockouts.
                                    •  1 AF 3-pole contactor with holding contact
                                    •  1 CB5-10 start contact block
                                    •  1 PE and 1 neutral terminal.
                                  1SBC133005V0014  Control supply wiring:

                                    IEC starters type: phase-to-phase, separate supply or phase-to-neutral.
                                    UL starters type: separate supply.

                                    TF42 thermal overload relay to be ordered separately and choses according to motor's nominal
          DRAF                      current (see table in the next page).
          + TF42 to be ordered separately
                                    DRAF enclosed DOL starters
                                    IEC - AC-3             Control supply   Rated control   Type   Order code  Weight
                                    Rated operational      wiring    circuit
                                    power           max.             voltage                               Pkg
                                    220 V 380 V  500 V 690 V  current  Uc min ... Uc max                   (1 pce)
                                    230 V 400 V     θ ≤ 40 °C        (1)
                                    240 V           Ue=400 V
                                    kW  kW   kW  kW  A               V 50/60 Hz                            kg
                                    IEC starters type
                                    2.2  4   5.5  5.5  9   Separate supply  24…60  DRAF09-11S  1SBK134237R1100  0.820
                                                           Phase-to-neutral  100...250  DRAF09-13N  1SBK134137R1300  0.820
                                                           Phase-to-phase  250...500  DRAF09-14P  1SBK134037R1400  0.820
                                    3   5.5  7.5  7.5  12  Separate supply  24…60  DRAF12-11S  1SBK154237R1100  0.820
                                                           Phase-to-neutral  100...250  DRAF12-13N  1SBK154137R1300  0.820
                                                           Phase-to-phase  250...500  DRAF12-14P  1SBK154037R1400  0.820
                                    4   7.5  9  9   18     Separate supply  24…60  DRAF16-11S  1SBK174237R1100  0.820
                                                           Phase-to-neutral  100...250  DRAF16-13N  1SBK174137R1300  0.820  10
                                                           Phase-to-phase  250...500  DRAF16-14P  1SBK174037R1400  0.820
                                    (1) Select DRAF..S with separate supply for 24...60 V DC control circuit voltage (change A2 - Us wire to blue color acc. to IEC 60947-4-1).



                                    UL starter type with separate control supply wiring
                                    UL / CSA                         Rated control   Type   Order code     Weight
                                    Horse power ratings              circuit
                                    Single phase motor Three phase motor  voltage                          Pkg
                                    120 V  240 V  200 V    220 V   440 V   550 V   Uc min ... Uc max       (1 pce)
                                                208 V  240 V  480 V  600 V

                                    hp    hp    hp   hp   hp   hp    V 50/60 Hz                            kg
                                    UL starters type
                                    0.75  1.5   2    2    5    7.5   24…60     DRAF09-11U  1SBK134238R1100  0.820
                                                                     100...250  DRAF09-13U  1SBK134238R1300  0.820
                                                                     250...500  DRAF09-14U  1SBK134238R1400  0.820
                                    1     2     3    3    7.5  10    24…60     DRAF12-11U  1SBK154238R1100  0.820
                                                                     100...250  DRAF12-13U  1SBK154238R1300  0.820
                                                                     250...500  DRAF12-14U  1SBK154238R1400  0.820
                                    1.5   3     5    5    10   15    24…60     DRAF16-11U  1SBK174238R1100  0.820
                                                                     100...250  DRAF16-13U  1SBK174238R1300  0.820
                                                                     250...500  DRAF16-14U  1SBK174238R1400  0.820
   828   829   830   831   832   833   834   835   836   837   838