Page 893 - ABB_Motor _Protection_and_Control_catalogue_20221216
P. 893

ABB  MOTOR PROTECTION AND CONTROL                                                13/3

          —

          Customer assembled motor starting solutions






          ABB Expertise                                       Website access:
          ABB has acquired years of experience with respect to problems   http://applications.it.abb.com/SOC/Page/Selection.aspx
          of coordination and is able to make a complete offer based on
          tests performed in its qualified laboratories. This offer covers
          400 V AC, 500 V AC, 690 V AC networks.              How to combine assemble and wire starter components
          A complete database of coordination tables, according to   The section "customer assembled motor stating solutions" in
          IEC 60947-4-1 (EN 60947-4-1), and UL 60947-4-1 between the   this catalog gives the components lists and wiring diagrams to
          branch circuit protective device and the motor starter is avail-  assemble the most typical motor starting solutions.
          able on the ABB Website.                            It covers direct-on-line Starters, reversing starters or star-delta
          In the coordination tables the following short-circuit protection   starters protected with manual motor starters or with thermal
          devices are recommended:                            overload relays for Type I or type II coordination for normal
          •  Case circuit-breakers (MCCBs)                    starting time.
          •  Miniature circuit-breakers (MCBs)                Note:
          •  Switch-disconnector-fuses (aM, gG and BS)        In order to confirm your starter combination ratings according
          •  Manual motor starters (MMS).                     to ABB's lattest coordination test results, or to see other
                                                                coordination of components please refer to the above
                                                                mentioned SOC tool. SOC tool get constant updates and
          Select Optimized Coordination tool (SOC)              additions
          Selected Optimized Coordination is a web tool for the selection
          of ABB products to be used in the following applications:
          •  Motor starting and protection                    General remarks applicable to all tables
          •  Selectivity between protection devices           •  Each table is defined for a maximum ambient temperature
          •  Back-up protection                                of 40 °C. For higher temperatures, apply a derating factor
                                                                 according to the following rules:
          •  Other devices protection.
                                                              •  Fuses: factor of 0.8 applied to In for an ambient temperature
                                                               of 70 °C
          In order to guarantee the best performance and the longest   •  MCCBs and MCBs: factor of 0.8 applied to In for an ambient
          lifetime, devices involved into the applications mentioned   temperature of 60 °C
          above (short-circuit protection devices, contactors, overload   •  The starter derating factor depends on the operating
          relays, softstarters, …) need to be coordinated.       conditions of thermal overload relays:
          •  The coordination among devices cannot be determined   •  Factor of 0.9 applied to In for an ambient temperature of 70 °C.
           directly: tests in power laboratories shall be carried out to   •  Each table is defined for motor currents: 3-phase motors,
           qualify the coordination type at low fault and high fault   4-pole
           currents, according to IEC or UL standards.        •   Normal starting means a starting time < 2 s. - Difficult
          •  ABB coordination tables are the results of such tests and     starting means an accelerating time 10 s < ts < 30 s
           represent the ABB offerings in terms of motor starting and   •  Tripping classes of thermal overload relays according to
           protection, selectivity, back-up and switch-disconnector
           protection.                                         IEC 60947-4-1 (EN 60947-4-1): 10A and 10
          •  In Selected Optimized Coordination all available ABB   •  Tripping classes of electronic overload relays according to
           coordination tables are stored and easily accessible.  IEC 60947-4-1 (EN 60947-4-1): 10E, 20E, 30E selectable
                                                              •  In the tables with MCCBs, these are fitted with the magnetic
                                                               relay alone. Setting is always carried out at > 12.3 Ie AC-3 so
                                                               that the transient current peak occurring during starting does
                                                               not lead to  tripping.








                                                                                                                      13
   888   889   890   891   892   893   894   895   896   897   898