Page 895 - ABB_Motor _Protection_and_Control_catalogue_20221216
P. 895

ABB  MOTOR PROTECTION AND CONTROL                                                13/5

          —

          DOL and reversing starters protected by manual motor starters
          With AF contactors - open type version in kit form







                                    Application
                                    Full voltage direct-on-line (DOL) starting and reversing starting for controlling three-phase
                                    asynchronous motors is a simple and economic solution characterised by a high starting
                             I >
                                    torque (1.9 to 2.1 times full-speed torque) and a starting current 5.5 to 7 times nominal cur-
                                    rent.
                                    I /In  C /Cn
                                    7
                                    6
                                                I
                                    5
                                                              I = current
                                    4                         C = torque
                                                              In = nominal current
                                    3                         Cn = nominal torque
                        1SFC101102V0001  2 1  C


                                    0  10  30    60  80  100
          DOL starter
          MS132-10K + BEA16-4KF     Coordination types
          + AF09-30-10K             The contactor and the manual motor starter control and protect motors against overload
                                    and short-circuits according to coordination types 1 and 2 (IEC 60947-4-1 / EN 60947-4-1)
                                    defining the anticipated level of service continuity as follow:
                                    Type 1:  In short-circuit conditions, the contactor or starter does not endanger persons or
                                          installations and will not be able to then operate without being repaired or having
                                          parts replaced.
                                    Type 2:  In short-circuit conditions, the contactor or starter does not endanger persons or
                                I >
                                          installations and will be able to operate afterwards. The risk of contacts light weld-
                                          ing is acceptable.

                                    Main Technical Data
                                    Standards                 IEC 60947-4-1 / EN 60947-4-1
                                    Rated operational voltage Ue max.  690 V - 50/60 Hz
                                    Rated insulation voltage Ui
                                     acc. to IEC 60947-4-1    690 V
                                     acc. to UL / CSA         600 V
                               1SFC101105V0001  Switching frequency  ≤ 15 starts/hour - 80 % max. load factor - with max. 1.5 s starting time
                                                              ≤ 30 starts/hour - 50 % max. load factor - with max. 1.5 s starting time
                                    Ambient air temperature
                                     Close to the device  use with MS116 ≤ 55 °C
                                                    use with MS132,
          Reversing starter                          MS165, MS495 ≤ 60 °C
          MS132-10K + BEA16-4KF
          + BER16-4KF + AF09-30-10K  Degree of protection     IP20

                                    Mounting positions

                                        Pos. 2  +30°  -30°                 Pos. 2  +30°  -30°                         13

                                     Pos. 4                             Pos. 4
                                              Pos. 3                              Pos. 3






                                          Pos. 1
                                                     Pos. 1 ± 30°
                                                                            Pos. 1      Pos. 1 ± 30°


                                               Pos. 5
                                                                                   Pos. 5
                                    DOL starters                       Reversing starters
   890   891   892   893   894   895   896   897   898   899   900