DOL and reversing starters protected by manual motor starters
With AF contactors - open type version in kit form
Application
Full voltage direct-on-line (DOL) starting and reversing starting for controlling three-phase
asynchronous motors is a simple and economic solution characterised by a high starting
I >
torque (1.9 to 2.1 times full-speed torque) and a starting current 5.5 to 7 times nominal cur-
rent.
I /In C /Cn
7
6
I
5
I = current
4 C = torque
In = nominal current
3 Cn = nominal torque
1SFC101102V0001 2 1 C
0 10 30 60 80 100
DOL starter Coordination types
MS132-10 + BEA16-4 + AF09-30-10
The contactor and the manual motor starter control and protect motors against overload
and short-circuits according to coordination types 1 and 2 (IEC 60947-4-1 / EN 60947-4-1)
defining the anticipated level of service continuity as follow:
Type 1: In short-circuit conditions, the contactor or starter does not endanger persons or
installations and will not be able to then operate without being repaired or having
parts replaced.
Type 2: In short-circuit conditions, the contactor or starter does not endanger persons or
I >
installations and will be able to operate afterwards. The risk of contacts light weld-
ing is acceptable.
Main Technical Data
Standards IEC 60947-4-1 / EN 60947-4-1
Rated operational voltage Ue max. 690 V - 50/60 Hz
Rated insulation voltage Ui
acc. to IEC 60947-4-1 690 V
acc. to UL / CSA 600 V
1SFC101105V0001 Switching frequency ≤ 15 starts/hour - 80 % max. load factor - with max. 1.5 s starting time
≤ 30 starts/hour - 50 % max. load factor - with max. 1.5 s starting time
Ambient air temperature
Close to the device use with MS116 ≤ 55 °C
use with MS132,
Reversing starter MS165, MS495 ≤ 60 °C
MS132-10 + BEA16-4 + BER16-4 Degree of protection IP20
+ VEM4 + AF09-30-10
Mounting positions
+30° -30° +30° -30°
Pos. 2 Pos. 2
13
Pos. 4 Pos. 4
Pos. 3 Pos. 3
Pos. 1 Pos. 1 ± 30° Pos. 1 Pos. 1 ± 30°
Pos. 5 Pos. 5
DOL starters Reversing starters