Page 900 - ABB_Motor _Protection_and_Control_catalogue_20221216
P. 900
13/10 ABB MOTOR PROTECTION AND CONTROL
—
Reversing starters protected by MS manual motor starters
Coordination type 1
Manual motor starters Contactors Accessories
I > BEA..-4KF BER..-4KF
+
VEM4K CA4-10K
IEC Type Order code Setting Rated Rated control circuit Type Order code Allowed Type Order code
AC-3, 400 V (1) range instantaneous voltage (3) setting
Rated short-circuit Uc min. ... Uc max. current
operational current setting (2)
power current Ii
kW A A A V 50/60 Hz V DC A
Coordination type 1, AC-3, 16 kA or 50 kA, 400 V, 50/60 Hz
0.06 0.2 MS132-0.25K 1SAM350010R1002 0.16...0.25 3.13 100...250 100...250 AF09-30-10K-13 1SBL137005R1310 0.25 BEA16-4KF 1SBN081325T1000
0.09 0.3 MS132-0.4K 1SAM350010R1003 0.25...0.40 5 100...250 100...250 AF09-30-10K-13 1SBL137005R1310 0.4 + BER16-4KF 1SBN081322R1000
0.12 0.44 MS132-0.63K 1SAM350010R1004 0.40...0.63 7.88 100...250 100...250 AF09-30-10K-13 1SBL137005R1310 0.63 + VEM4K 1SBN030113R1000
0.18 0.6 MS132-0.63K 1SAM350010R1004 0.40...0.63 7.88 100...250 100...250 AF09-30-10K-13 1SBL137005R1310 0.63
0.25 0.85 MS132-1.0K 1SAM350010R1005 0.63...1.00 12.5 100...250 100...250 AF09-30-10K-13 1SBL137005R1310 1
0.37 1.1 MS132-1.6K 1SAM350010R1006 1.00...1.60 20 100...250 100...250 AF09-30-10K-13 1SBL137005R1310 1.6
0.55 1.5 MS132-1.6K 1SAM350010R1006 1.00...1.60 20 100...250 100...250 AF09-30-10K-13 1SBL137005R1310 1.6
0.75 1.9 MS132-2.5K 1SAM350010R1007 1.60...2.50 31.25 100...250 100...250 AF09-30-10K-13 1SBL137005R1310 2.5
1.1 2.7 MS132-4.0K 1SAM350010R1008 2.50...4.00 50 100...250 100...250 AF09-30-10K-13 1SBL137005R1310 4
1.5 3.6 MS132-4.0K 1SAM350010R1008 2.50...4.00 50 100...250 100...250 AF09-30-10K-13 1SBL137005R1310 4
2.2 4.9 MS132-6.3K 1SAM350010R1009 4.00...6.30 78.75 100...250 100...250 AF09-30-10K-13 1SBL137005R1310 6.3
3 6.5 MS132-10K 1SAM350010R1010 6.30...10.0 150 100...250 100...250 AF09-30-10K-13 1SBL137005R1310 9
4 8.5 MS132-10K 1SAM350000R1010 6.30...10.0 150 100...250 100...250 AF09-30-10K-13 1SBL137005R1310 9
5.5 11.5 MS132-12K 1SAM350010R1012 8.00...12.0 180 100...250 100...250 AF12-30-10K-13 1SBL157005R1310 12
7.5 15.5 MS132-16K 1SAM350010R1011 10.0...16.0 240 100...250 100...250 AF16-30-10K-13 1SBL177005R1310 16
11 22 MS132-25K 1SAM350010R1014 20.0...25.0 375 100...250 100...250 AF26-30-00K-13 1SBL237005R1300 25 BEA38-KF 1SBN082325T2000
15 29 MS132-32K 1SAM350010R1015 25.0...32.0 480 100...250 100...250 AF30-30-00K-13 1SBL277005R1300 32 + BER38-4KF 1SBN082332R1000
+ VEM4K 1SBN030113R1000
-2x CA4-10K 1SBN010160R1010
Coordination type 2, AC-3, 16 kA or 50 kA, 400 V, 50/60 Hz
0.06 0.2 MS132-0.25K 1SAM350010R1002 0.16...0.25 3.13 100...250 100...250 AF09-30-10-13 1SBL137001R1310 0.25 BEA16-4KF 1SBN081325T1000
0.09 0.3 MS132-0.4K 1SAM350000R1003 0.25...0.40 5 100...250 100...250 AF09-30-10K-13 1SBL137005R1310 0.4 + BER16-4KF 1SBN081322R1000
0.12 0.44 MS132-0.63K 1SAM350010R1004 0.40...0.63 7.88 100...250 100...250 AF09-30-10K-13 1SBL137005R1310 0.63 + VEM4K 1SBN030113R1000
0.18 0.6 MS132-0.63K 1SAM350010R1004 0.40...0.63 7.88 100...250 100...250 AF09-30-10K-13 1SBL137005R1310 0.63
0.25 0.85 MS132-1.0K 1SAM350010R1005 0.63...1.00 12.5 100...250 100...250 AF09-30-10K-13 1SBL137005R1310 1
0.37 1.1 MS132-1.6K 1SAM350010R1006 1.00...1.60 20 100...250 100...250 AF09-30-10K-13 1SBL137005R1310 1.6
0.55 1.5 MS132-1.6K 1SAM350010R1006 1.00...1.60 20 100...250 100...250 AF09-30-10K-13 1SBL137005R1310 1.6
0.75 1.9 MS132-2.5K 1SAM350010R1007 1.60...2.50 31.25 100...250 100...250 AF09-30-10K-13 1SBL137005R1310 2.5
1.1 2.7 MS132-4.0K 1SAM350010R1008 2.50...4.00 50 100...250 100...250 AF26-30-00K-13 1SBL237005R1300 4
1.5 3.6 MS132-4.0K 1SAM350010R1008 2.50...4.00 50 100...250 100...250 AF26-30-00K-13 1SBL237005R1300 4
2.2 4.9 MS132-6.3K 1SAM350010R1009 4.00...6.30 78.75 100...250 100...250 AF26-30-00K-13 1SBL237005R1300 6.3
3 6.5 MS132-10K 1SAM350010R1010 6.30...10.0 150 100...250 100...250 AF26-30-00K-13 1SBL237005R1300 10 BEA38-KF 1SBN082306T2000
4 8.5 MS132-10K 1SAM350010R1010 6.30...10.0 150 100...250 100...250 AF26-30-00K-13 1SBL237005R1300 10 + BER38-4KF 1SBN082322R1000
5.5 11.5 MS132-12K 1SAM350010R1012 8.00...12.0 180 100...250 100...250 AF26-30-00K-13 1SBL237005R1300 12 + VEM4K 1SBN030113R1000
13
7.5 15.5 MS132-16K 1SAM350010R1011 10.0...16.0 240 100...250 100...250 AF30-30-00K-13 1SBL277005R1300 16 +2x CA4-10K 1SBN01060R1010
11 22 MS132-25K 1SAM350010R1014 20.0...25.0 375 100...250 100...250 AF30-30-00K-13 1SBL277005R1300 25
15 29 MS132-32K 1SAM350010R1015 25.0...32.0 480 100...250 100...250 AF30-30-00K-13 1SBL277005R1300 32
(1) MS116 manual motor starter can be selected according to the current setting range indicated on the coordination line, up to:
- 15 kW, 400 V - AC-3 at 16 kA
- 4 kW, 400 V - AC-3 at 50 kA.
(2) For other control voltages, see "Voltage code table".
(3) AF38 3-pole contactor can be selected for coordination type 1, 16 kA and 50 kA, 18.5 kW, 400 V - AC-3 (BEA65-4 available for AF40 ... AF65 only).
(4) For direct mounting on 2 rails 35 mm of MS165 with AF40 ... AF65: BEA65-4 must be associated with BPR65-4 fixed on each contactor base. Applicable for MS165 manufac-
tured
after week 31, 2016 (date code > 16114).
(5) AF ... -11 not suitable for direct control by PLC-output.
(3) AF26 3-pole contactor can be selected for coordination type 2, 16 kA, 7.5 kW, 400 V - AC-3.
AF38 3-pole contactor can be selected for coordination type 2, 16 kA and 50 kA, 18.5 kW, 400 V - AC-3 (BEA65-4 available for AF40 ... AF65 only).
(4) BEA26-4 should be selected with MS116-12 … MS116-16 and AF26 … AF38.
BEA38-4 can only be selected with MS116-20 … MS116-32.
(5) For direct mounting on 2 rails 35 mm of MS165 with AF40 ... AF65: BEA65-4 must be associated with BPR65-4 fixed on each contactor base. Applicable
for MS165 manufactured after week 31, 2016 (date code > 16114).