Page 904 - ABB_Motor _Protection_and_Control_catalogue_20221216
P. 904

13/14            ABB  MOTOR PROTECTION AND CONTROL

          —

          DOL and reversing starters protected by manual motor starters
          With AF contactors - open type version in kit form
          Wiring diagrams


          Direct-on-line starters
          Power circuit                     1-phase              AC or DC local control  AC or DC remote control
                                                                    KM1:5/L3               KM1:5/L3
                                                                                                  Q1
                               1/L1  3/L2  5/L3    1/L1  3/L2  5/L3     Us  33  Q1  34     Us  33  34
                                     33  43             33  43
                     Q1
                                     34  44             34  44
                              I> I> I>            I> I> I>                     O                 O
                               2/T1  4/T2  6/T3    2/T1  4/T2  6/T3               13                     13
                                                                            I   KM1              I     KM1
                               1/L1  3/L2  5/L3    1/L1  3/L2  5/L3               14                     14
                           A1        13                 13
                        KM1
                           A2        14                 14                        A1                     A1
                               2/T1  4/T2  6/T3    2/T1  4/T2  6/T3     Us  Q1  KM1           Us  Q1  KM1
                                                                    N  43  44     A2       N  43  44     A2


                                                                    KM1:3/L2               KM1:3/L2
                                 V
                               U   W             U  V
                                M                 M               Note: coil Uc 12-20 V DC : A1+, A2-
                                ~
                                                  ~
          Reversing starters
          Power circuit                                    AC or DC local control
                                                               KM2:5/L3

                     1/L1  3/L2  5/L3                          Us     33  Q1  34
                           33  43                                               O
          Q1
                           34  44
                    I> I> I>
                                                                           .3     .3
                     2/T1  4/T2  6/T3                                 I  KM1  II   KM2
                                                                           .4     .4
                                                                                              With VM
                     1/L1  3/L2  5/L3     1/L1  3/L2  5/L3  With VEM4     01      01                 21      21
                 A1                   A1                                 (2)       (2)             KM2    KM1
              KM1                  KM2                                                               22      22
                                                                                                    A1      A1
                 A2                   A2                                KM1         KM2           KM1         KM2
                     2/T1  4/T2  6/T3     2/T1  4/T2  6/T3     Us  43  Q1  44  A2  (1)  A2          A2      A2
                                                               N
                                                                              (3)
                                                               KM2:3/L2
                                                           AC or DC remote control
                     U  V  W
                      M                                        KM2:5/L3 33  Q1  34
                      ~


                                                               Us
                                                                    O
                                                                 II
   13
                                                                           .3     .3
                                                                         KM1    KM2
                                                                           .4     .4
                                                                  I
                                                                                              With VM
                                                           With VEM4
                                                                          01     01                  21      21
                                                                         (2)       (2)             KM2    KM1
                                                                                                     22      22
                                                                                                    A1      A1
                                                                        KM1         KM2           KM1         KM2
                                                                  Us  43  Q1  44  A2  (1)  A2       A2      A2
                                                              N
                                                                              (3)
                                                               KM2:3/L2
                                                            Note:  - VEM4 = VM4 (1) + VE4 (2) with A2-A2 (3) connection
                                                                (Except for coil Uc 12-20 V DC : use VM4 with CA4).
                                                                - coil Uc 12-20 V DC : A1+, A2-
   899   900   901   902   903   904   905   906   907   908   909