Page 984 - ABB_Motor _Protection_and_Control_catalogue_20221216
P. 984

10/10            ABB  MOTOR PROTECTION AND CONTROL

          —

          Coordination with short-circuit protection devices






                                                               does not endanger persons or installations and will not be
          Definition
          The coordination of control and protection devices in   able to then operate without being repaired or having parts
                                                               replaced.
          compliance with IEC 60947-4-1, EN 60947-4-1 and UL 60947-4-1
          between the branch circuit protective device and the motor   •  Type 2: In short-circuit conditions, the contactor or starter
          starter standards defines for the contactors and starters the   does not endanger persons or installations and will be able to
          type rating and characteristics of the short-circuit protection   operate afterwards. The risk of contacts light welding is ac-
          devices SCPD which allow selective protection against   ceptable. In this case, the manufacturer must stipulate the
          overloads and ensure protection against short circuits.   measures to be taken with respect to maintenance of the
                                                               equipment.
          Basic functions
          Any starter is designed to:                         Combination Motor Controllers (CMC)
                                                              Article 409 of the National Electrical Code (NFPA 70) re-
          •  start motors
                                                              quires industrial control panels to be marked with a SCCR
          •  ensure continuous functioning of motors          (Short-Circuit Current Rating). According to the National
                                                              Electrical Code (NEC), UL 508A Supplement SB - Standard
          •  disconnect motors from the supply line
                                                              for Industrial Control Panels - provides an accepted method
          •  guarantee protection of motors against overloads.  for determining the SCCR of the control panel. Industrial
                                                              control panel manufacturers can use Selected Optimized Co-
          The starter is typically made up of a switching device   ordination tool (SOC) for guidance. SOC tool is intended for
          (contactor) and an overload protection device (thermal overload   those manufacturers that purchase the discrete compo-
          relay or electronic overload relay). These two devices MUST be   nents and assemble combination motor controllers within
          coordinated with each other and with equipment capable of   their panels to achieve a combination SCCR that is higher
          providing protection against short-circuit: typically a circuit   than the lowest-rated individual component.
          breaker with magnetic release only or a switch fuse. These are
          not necessarily part of the starter.
                                                              Failure of components under fault conditions can lead to
                                                              safety concerns for personnel working in close proximity to
          Applicable standards                                electrical equipment. The harmonized UL 60947-4-1 and CSA
          IEC 60947-4-1 (EN 60947-4-1) and UL 60947-4-1 precisely de-  C22.2 No.60947-4-1 standards define acceptance criteria for
          fines the different points to be considered between the branch   these components.
          circuit protective device and the motor starter in order to carry
          out correct coordination. Complete coordination for a combina-  Several criteria exist for all devices:
          tion includes the below points.
                                                                  - The short-circuit protective device successfully interrupts
          •  Selectivity test between the overload relay and the Short-Cir-  the fault
           cuit Protection Device (SCPD).                         - The enclosure door has not blown open, and it remains pos-
                                                                 sible to open it manually
          •  Short-circuit condition tests at prospective “r” currents     - No damage to, or separation between, the conductors and
           These currents depend on the rated operational current of the   the terminals
           starter (Ie AC-3 / AC-3e) and are given by the standard     - No damage to the insulating bases of live parts, and no ac-
           (Table 13).                                           cess to current carrying parts.
           For example:
             -  r = 1 kA for Ie AC-3/AC-3e ≤ 16 A             For Combination Motor Controllers, the included cir-
             -  r = 3 kA for 16 A < Ie AC-3/AC-3e ≤ 63 A      cuit-breaker / manual motor starter or switch should be ca-
             -  r = 5 kA for 63 A < Ie AC-3/AC-3e ≤ 125 A etc.  pable of being manually operated, and should not be dam-
          •  Short-circuit condition tests at the rated conditional   aged, exposing conductive parts.
           short-circuit current “Iq”.
           This is the maximum prospective current that the combina-
           tion can withstand, for example 50 kA.

          Types of coordination
          IEC 60947-4-1 (EN 60947-4-1) UL 60947-4-1 defines two types of
          coordination between the branch circuit protective device and
          the motor starter according to the expected level of service con-
          tinuity. Acceptable extreme damage for the switchgear is di-
   14
          vided into two types.
          •  Type 1: In short-circuit conditions, the contactor or starter
   979   980   981   982   983   984   985   986   987   988   989