S 200 80A-100A series technical features
S 200 80A-100A
General Data
Standards IEC/EN 60898-1, IEC/EN 60947-2
Poles 1P, 2P, 3P, 4P, 1P+N, 3P+N
Tripping characteristics B, C
Rated current I 80 A, 100 A
n
Rated frequency f 50/60 Hz
S 200 80-100A Rated insulation voltage Ui acc. to IEC/EN 440 V AC
60664-1 (VDE 0110-1)
Overvoltage category III
Pollution degree 2
IEC/EN 60898-1
Rated operational voltage U 1P: 230/400 V AC; 1P+N: 230 V AC; 2P, 3P, 4P, 3P+N: 400 V AC
n
Max. power frequency recovery voltage U 1P: 253/440 V AC; 1P+N: 253 V AC; 2P, 3P, 4P, 3P+N: 440 V AC
max
Min. operating voltage 12 V AC
Rated short-circuit capacity I cn 6 kA
Rated impulse withstand voltage U imp 4 kV (test voltage 6.2 kV at sea level, 5 kV at 2,000 m)
(1.2/50µs)
Dielectrical test voltage 2 kV (50/60 Hz, 1 min.)
Reference temperature for tripping B, C: 30 °C
characteristics
Electrical endurance 10,000 ops. (AC); one cycle 2 s - ON, 28 s - OFF
IEC/EN 60947-2
Rated operational voltage U 1P, 1P+N: 230 V AC; 2P, 3P, 4P, 3P+N: 400 V AC
e
Max. power frequency recovery voltage U max 1P, 1P+N: 253 V AC; 2P, 3P, 4P, 3P+N: 440 V AC
Min. operating voltage 12 V AC
Rated ultimate short-circuit breaking capacity I cu 6 kA
Rated service short-circuit breaking capacity I cs 6 kA
Rated impulse withstand voltage U imp 4 kV (test voltage 6.2 kV at sea level, 5 kV at 2,000 m)
(1.2/50 µs)
Dielectrical test voltage 2 kV (50/60 Hz, 1 min.)