Page 117 - Din prodcuts 2020
P. 117

1/107      1




          —
          MCBs
          S 200 80A-100A series technical features




 S 200 80A-100A                     Reference temperature for tripping   B, C:  55 °C
                                    characteristics
 General Data
                                    Electrical endurance              10,000 ops. (AC); one cycle 2 s - ON, 28 s - OFF
 Standards    IEC/EN 60898-1, IEC/EN 60947-2
                                    Mechanical data
 Poles  1P, 2P, 3P, 4P, 1P+N, 3P+N
                                    Housing                           Insulation group I, RAL 7035
 Tripping characteristics  B, C
                                    Toggle                            Insulation group II, black, sealable
 Rated current I     80 A, 100 A
 n
 Rated frequency f  50/60 Hz        Contact position indication       Real CPI (red ON/green OFF)
                                    Protection degree acc. to DIN EN 60529  IP20 , IP40 in enclosure with cover
                                                                         1)
 Rated insulation voltage Ui acc. to IEC/EN   440 V AC
 60664-1 (VDE 0110-1)               Mechanical endurance              20,000 ops.
 Overvoltage category  III          Shock resistance acc. to DIN EN 60068-2-27  25 g, 2 shocks, 13 ms
 Pollution degree  2                Vibration resistance acc. to DIN EN 60068-2-6  5 g, 20 cycles at 5…150…5 Hz at 0.8 I n
 IEC/EN 60898-1                     Environmental conditions (Damp heat cyclic)   28 cycles with 55 °C/90-96 % and 25 °C/95-100 %
                                    acc. to DIN EN 60068-2-30
 Rated operational voltage U     1P: 230/400 V AC; 1P+N: 230 V AC; 2P, 3P, 4P, 3P+N: 400 V AC
 n
 Max. power frequency recovery voltage U  1P: 253/440 V AC; 1P+N: 253 V AC; 2P, 3P, 4P, 3P+N: 440 V AC  Ambient temperature  -25 ... +55 °C
 max
 Min. operating voltage  12 V AC    Storage temperature               -40 ... +70 °C
                                                                      S 200 80A-100A
 Rated short-circuit capacity I  cn  6 kA
 Rated impulse withstand voltage U imp    4 kV (test voltage 6.2 kV at sea level, 5 kV at 2,000 m)  Installation
 (1.2/50µs)                         Terminal                          Failsafe bi-directional cache clamp
 Dielectrical test voltage  2 kV (50/60 Hz, 1 min.)   Cross-section of conductors (top/bottom)  solid, stranded: 50 mm  / 50 mm  2
                                                                                      2
                                                                      flexible: 50 mm  / 50 mm  2
                                                                                 2
 Reference temperature for tripping   B, C: 30 °C
 characteristics                    Cross-section of busbars (top/bottom)  16 mm  / 16 mm  2
                                                                           2
 Electrical endurance  10,000 ops. (AC); one cycle 2 s - ON, 28 s - OFF  Torque  3.0 Nm
 IEC/EN 60947-2                     Screwdriver                       Nr. 2 Pozidriv
 Rated operational voltage U  1P, 1P+N: 230 V AC; 2P, 3P, 4P, 3P+N: 400 V AC   Mounting  On DIN rail 35 mm acc. to EN 60715 by fast clip
 e
 Max. power frequency recovery voltage U max  1P, 1P+N: 253 V AC; 2P, 3P, 4P, 3P+N: 440 V AC  Mounting position  any
 Min. operating voltage  12 V AC    Supply                            any
 Rated ultimate short-circuit breaking capacity I cu  6 kA  Dimensions and weight
 Rated service short-circuit breaking capacity I cs  6 kA  Mounting dimensions acc. to DIN 43880  Mounting dimension 1
 Rated impulse withstand voltage U imp     4 kV (test voltage 6.2 kV at sea level, 5 kV at 2,000 m)  Pole dimensions (H x T x B)  88.8 x 69 x 17.5
 (1.2/50 µs)                        Pole weight                       approx. 126 g
 Dielectrical test voltage  2 kV (50/60  Hz, 1 min.)  Combination with auxiliary elements
                                    Auxiliary contact                 Yes
                                    Signal/auxiliary contact          Yes
                                    Shunt trip                        Yes
                                    Unervoltage release               Yes
                                    Motor Operating Device            Yes
   112   113   114   115   116   117   118   119   120   121   122