MCBs
S 200 80A-100A series technical features
S 200 80A-100A Reference temperature for tripping B, C: 55 °C
characteristics
General Data
Electrical endurance 10,000 ops. (AC); one cycle 2 s - ON, 28 s - OFF
Standards IEC/EN 60898-1, IEC/EN 60947-2
Mechanical data
Poles 1P, 2P, 3P, 4P, 1P+N, 3P+N
Housing Insulation group I, RAL 7035
Tripping characteristics B, C
Toggle Insulation group II, black, sealable
Rated current I 80 A, 100 A
n
Rated frequency f 50/60 Hz Contact position indication Real CPI (red ON/green OFF)
Protection degree acc. to DIN EN 60529 IP20 , IP40 in enclosure with cover
1)
Rated insulation voltage Ui acc. to IEC/EN 440 V AC
60664-1 (VDE 0110-1) Mechanical endurance 20,000 ops.
Overvoltage category III Shock resistance acc. to DIN EN 60068-2-27 25 g, 2 shocks, 13 ms
Pollution degree 2 Vibration resistance acc. to DIN EN 60068-2-6 5 g, 20 cycles at 5…150…5 Hz at 0.8 I n
IEC/EN 60898-1 Environmental conditions (Damp heat cyclic) 28 cycles with 55 °C/90-96 % and 25 °C/95-100 %
acc. to DIN EN 60068-2-30
Rated operational voltage U 1P: 230/400 V AC; 1P+N: 230 V AC; 2P, 3P, 4P, 3P+N: 400 V AC
n
Max. power frequency recovery voltage U 1P: 253/440 V AC; 1P+N: 253 V AC; 2P, 3P, 4P, 3P+N: 440 V AC Ambient temperature -25 ... +55 °C
max
Min. operating voltage 12 V AC Storage temperature -40 ... +70 °C
S 200 80A-100A
Rated short-circuit capacity I cn 6 kA
Rated impulse withstand voltage U imp 4 kV (test voltage 6.2 kV at sea level, 5 kV at 2,000 m) Installation
(1.2/50µs) Terminal Failsafe bi-directional cache clamp
Dielectrical test voltage 2 kV (50/60 Hz, 1 min.) Cross-section of conductors (top/bottom) solid, stranded: 50 mm / 50 mm 2
2
flexible: 50 mm / 50 mm 2
2
Reference temperature for tripping B, C: 30 °C
characteristics Cross-section of busbars (top/bottom) 16 mm / 16 mm 2
2
Electrical endurance 10,000 ops. (AC); one cycle 2 s - ON, 28 s - OFF Torque 3.0 Nm
IEC/EN 60947-2 Screwdriver Nr. 2 Pozidriv
Rated operational voltage U 1P, 1P+N: 230 V AC; 2P, 3P, 4P, 3P+N: 400 V AC Mounting On DIN rail 35 mm acc. to EN 60715 by fast clip
e
Max. power frequency recovery voltage U max 1P, 1P+N: 253 V AC; 2P, 3P, 4P, 3P+N: 440 V AC Mounting position any
Min. operating voltage 12 V AC Supply any
Rated ultimate short-circuit breaking capacity I cu 6 kA Dimensions and weight
Rated service short-circuit breaking capacity I cs 6 kA Mounting dimensions acc. to DIN 43880 Mounting dimension 1
Rated impulse withstand voltage U imp 4 kV (test voltage 6.2 kV at sea level, 5 kV at 2,000 m) Pole dimensions (H x T x B) 88.8 x 69 x 17.5
(1.2/50 µs) Pole weight approx. 126 g
Dielectrical test voltage 2 kV (50/60 Hz, 1 min.) Combination with auxiliary elements
Auxiliary contact Yes
Signal/auxiliary contact Yes
Shunt trip Yes
Unervoltage release Yes
Motor Operating Device Yes