1/110            ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS   2CHC 420 001 C0201
  1



          —
          SMCBs
          S750 series DR technical features




                                                                         S 750 DR
                            General Data  Standards                      IEC/EN 60947-2
                                      Poles                              1P, 2P, 3P, 4P
                                      Tripping characteristics           E   , K
                                                                          selective  selective
                                      Rated current I n             A    16…63
                                      Rated frequency f             Hz   50 / 60
                            Electrical   Rated operational voltage U e  V AC  230  (1-pole), 400 (2-, 3-, 4-pole)
                            Data
          S750 DR                     Rated breaking capacity I     kA   25
                            acc. to IEC/                cu
                            EN 60947-2  Rated service breaking capacity I cs  kA  12.5
                                      Rated insulation voltage U i  V    690
                                      Selectivity limit current Is1      rated breaking capacity of downstream breaker (min.) –
                                                                         see selectivity tables
                                      Overvoltage category               IV
                                      Pollution degree                   3
                                      Rated impulse withstand voltage U     kV  6
                                                              imp.
                                      Impulse withstand voltage acc. to   kV  8
                                      IEC 60364-5-53 (at 2000m above sea
                                      level)
                                      Impulse withstand test voltage   kV  9.8
                                      (1.2/50µs)
                                      Isolation function acc. to IEC 60364-5-53  yes
                                      Dielectric test voltage (50/60 Hz, 1 min.)  kV  2 (50 / 60 Hz, 1 min.)
                            Mechanical   Contact position indication     via toggle (I-ON / O-OFF),
                            Data                                         via trip indicator (red-ON / green-OFF)
                                      IP protection degree acc. to IEC/EN   IP40 (when protected by cabinet cover)
                                      60529
                                      Shock resistance acc. to IEC / EN 60068-  25 g, min. 3 shocks, duration 13 ms
                                      2-27
                                      Vibration resistance acc. to IEC/EN   2 g, 20 cycles 5…150…5 Hz
                                      60068-2-6
                                      Environmental conditions (damp heat   °C/  28 cycles: 55 / 90…96  –  25 / 95…100
                                      cyclic) acc. to IEC/EN 60068-2-30  RH
                                      Ambient temperature           °C   -25 … +55
                                      Storage temperature           °C   -40 … +70
                            Installation  Wire connection (Top)          frame terminal to connect solid and rigid stranded
                                                                         conductors incl. flexible conductors 2.5…50 mm²
                                      Wire connection (Bottom)           frame terminal to connect solid and rigid stranded
                                                                         conductors incl. flexible conductors 2.5…50 mm²
                                      Max. torque                   Nm   2.5 … 3
                                      Recommended Screwdriver            slotted: 1 x 5.5, Pozidrive: PZ 2
                                      Mounting                           DIN rail 35 mm acc. to EN 60715
                                      Locking                            integrated blocking device, additional locking by 3 mm
                                                                         padlock, 1mm seal wire or cabel binder
                                      Mounting position                  any
                                      Supply                             any
                            Dimensions   Size acc. to DIN 43880          3
                            and weight  Width                       mm   27 (per pole)
                                      Pole dimensions (H x D x W)   mm   see drawings
                                      Pole weight                   g    see order tables