Page 326 - Din prodcuts 2020
P. 326

2/134            ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS   2CHC 420 001 C0201




          —
  2
          DSE201
          Technical features and overall dimensions




          Electrical features
          Standards                                                  IEC 61009-1; IEC 61009-2-2; AS/NZS 61009
          Type (wave form of the earth leakage sensed)               AC, A
          Number of poles                                            1P+N
          Rated current I                                   A        6≤ In ≤ 50
                    n
          Rated sensitivity I  Δn                           mA       30
          Rated voltage U e                                 V        230-240
          Insulation voltage U                              V        500 V AC
                        i
          Overvoltage category                                       III
          Pollution degree                                           2
          Max. operating voltage                            V        264
          Min. operating voltage for protection against     V        85
          IΔn residual sinusoidal alternating currents
          Operating voltage of circuit test                 V        195 - 264
          Rated frequency                                   Hz       50/60
          Rated breaking capacity acc. to IEC 61009  ultimate I  A   6000
                                                    cn
          Rated residual breaking capacity I Δm             kA       6
          Rated impulse withstand voltage (1.2/50) U        kV       4 kV (test voltage 6.2kV at sea level, 5kV at 2000m)
                                         imp
          Dielectric test voltage at ind. freq. for 1 min.  kV       2.5 kV (50 / 60Hz, 1 min.)
          Thermomagnetic release - characteristic  B: 3 I  ≤ I  ≤ 5 I  n
                                                 n  m  n
                                             C: 5 I  ≤ I  ≤ 10 I  n  n
                                                   m
                                                 n
          Surge current resistance (wave 8/20)              A        NA
          Mechanical data
          Housing                                                    insulation group II, RAL 7035
          Toggle                                                     insulation group IIIA, black, sealable in ON-OFF positions
          Contact position indication                                CPI on toggle (I ON / 0 OFF)
          Electrical life                                   operations 10000
          Mechanical life                                   operations 20000
          Protection degree                  housing                 IP4X
                                             terminals               IP2X
          Shock resistance acc. to IEC/EN 60068-2-27                 30g - 2 shocks - 13ms
          Vibration resistance acc. to IEC/EN 60068-2-6              0.35mm or 5g - 20 cycles at 5…150…5 Hz without load
          Environmental conditions (damp heat)              °C/RH    28 cycles with 55°C/90-96% and 25°C/95-100%
          acc. to IEC/EN 60068-2-30
          Reference temperature for setting                 °C       30
          of thermal element
          Ambient temperature                               °C       -25…+55
          (with daily average ≤ +35 °C)
          Storage temperature                               °C       -40…+70
   321   322   323   324   325   326   327   328   329   330   331