Page 326 - Din prodcuts 2020
P. 326
2/134 ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS 2CHC 420 001 C0201
—
2
DSE201
Technical features and overall dimensions
Electrical features
Standards IEC 61009-1; IEC 61009-2-2; AS/NZS 61009
Type (wave form of the earth leakage sensed) AC, A
Number of poles 1P+N
Rated current I A 6≤ In ≤ 50
n
Rated sensitivity I Δn mA 30
Rated voltage U e V 230-240
Insulation voltage U V 500 V AC
i
Overvoltage category III
Pollution degree 2
Max. operating voltage V 264
Min. operating voltage for protection against V 85
IΔn residual sinusoidal alternating currents
Operating voltage of circuit test V 195 - 264
Rated frequency Hz 50/60
Rated breaking capacity acc. to IEC 61009 ultimate I A 6000
cn
Rated residual breaking capacity I Δm kA 6
Rated impulse withstand voltage (1.2/50) U kV 4 kV (test voltage 6.2kV at sea level, 5kV at 2000m)
imp
Dielectric test voltage at ind. freq. for 1 min. kV 2.5 kV (50 / 60Hz, 1 min.)
Thermomagnetic release - characteristic B: 3 I ≤ I ≤ 5 I n
n m n
C: 5 I ≤ I ≤ 10 I n n
m
n
Surge current resistance (wave 8/20) A NA
Mechanical data
Housing insulation group II, RAL 7035
Toggle insulation group IIIA, black, sealable in ON-OFF positions
Contact position indication CPI on toggle (I ON / 0 OFF)
Electrical life operations 10000
Mechanical life operations 20000
Protection degree housing IP4X
terminals IP2X
Shock resistance acc. to IEC/EN 60068-2-27 30g - 2 shocks - 13ms
Vibration resistance acc. to IEC/EN 60068-2-6 0.35mm or 5g - 20 cycles at 5…150…5 Hz without load
Environmental conditions (damp heat) °C/RH 28 cycles with 55°C/90-96% and 25°C/95-100%
acc. to IEC/EN 60068-2-30
Reference temperature for setting °C 30
of thermal element
Ambient temperature °C -25…+55
(with daily average ≤ +35 °C)
Storage temperature °C -40…+70