4/77
—
Auxiliary elements for S800
S800-SCL-SR
4
S803HV-SCL-SR in combination with S803HV-K
General data
Standard IEC 60947-2
Poles 3
Rated frequency f Hz 50/60
Data acc. to IEC 60947-2
Rated operational voltage U V AC 580/1000
e
Rated operational current I A 32, 63, 100
n
Rated ultimate short-circuit breaking capacity I cu kA 15
Rated service short-circuit capacity I kA 10
cs
Rated insulation voltage U V AC 1000
i
Rated impulse withstand voltage U imp kV 8
Mechanical data
Housing Material group I, RAL 7035
Toggle black, lockable
Protection degree acc. to IEC / EN 60529 IP20; IP40 (actuating side only)
Classification acc. to NF F16-101, NF F 16-102 I3, F2
Classification acc. to IEC 61373 Cat. 1, Class B
(shock and vibration)
Shock resistance acc. to IEC / EN 60068-2-27 Test Ea: 5 g / 30 ms
Vibration resistance acc. to IEC / EN 60068-2-6 Test Fc:
2–13.2 Hz / 1 mm
13.2–100 Hz / 0.7 g
with load 100 % x I
e
Environmental conditions (damp heat) 12+12 cycle with 55 °C / 90 - 96 % RH
acc. to IEC / EN 60068-2-30 and 25 °C / 95 - 100 % RH
Environmental conditions (dry heat) 16 hours 55 °C / 2 hours 70 °C / 55 % RH
acc. to IEC / EN 60068-2-2
Ambient temperature °C -25 … +60
Storage temperature °C -40 … +70
Installation
Terminal Failsafe cage terminal
Connection (top/bottom) – C only mm 2 1 … 50 solid / stranded
u
1 … 70 flexible
Tightening torque Nm 3.5
Screwdriver POZI 2
Mounting EN 60715
Mounting position any
Supply side any
Dimension and weight
Pole dimension (H x L x W) mm 142 x 76.5 x 26.5
Pole weight kg 0.25