4/74             ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS   2CHC 420 001 C0201




          —
          Auxiliary elements for S800
          S800-SCL




  4
                                    S803S-SCL
                                    Short-circuit current limiter
                                    The S803S used together with an S803S-SCL ensures reliable switch-off of short-circuit
                                    currents up to 100 kA, at an operating voltage of 440 V AC and over the entire rated current
                                    range of up to 125 A.
                                    For applications at 690 V AC,  the combination of S803S-SCL ensures reliable short-circuit
                                    protection up to 50 kA; here also, this is ensured over the entire rated current range up to
                                    125 A, typical for the S800.


                                                       Rated              Ultimate short-circuit   Service short-circuit
                                    Example combinations  operational voltage U e  breaking capacity I cu  breaking capacity I cs
                                    S803S-SCL125 +     440 V AC           100 kA             100 kA
                                    S803S-C125         690 V AC             50 kA              50 kA
                                    S803S-SCL63 +      440 V AC           100 kA             100 kA
                                    S803S-K63          690 V AC             50 kA              50 kA
                                    S803S-SCL32 +      440 V AC           100 kA             100 kA
                                    S803S-B16          690 V AC             50 kA              50 kA


                                    Short-circuit current limiter S803S-SCL
                                    Rated operational current I e            A          32, 63, 125
                                    Pole                                                3
                                    Rated operational voltage U   e
                                    (AC) 50/60 Hz                            V          400/690
                                    Rated insulation voltage U i             V          690
                                    Rated impulse withstand voltage U        kV         8
                                                            imp
                                    Rated ultimate short-circuit breaking capacity I
                                                                    cu
                                    compliant to IEC 60947-2
                                    400 VAC                                  kA         100
                                    440 VAC                                  kA         100
                                    690 VAC                                  kA         50
                                    Rated service short-circuit breaking capacity I     100% I cu
                                                                   cs
                                    compliant to IEC 60947-2
                                    Rated frequency                          Hz         50/60
                                    Mounting position                                   any
                                    Disconnector properties compliant to IEC 60947-2    yes
                                    Standard                                            IEC 60947-2
                                    Connections C  (32 A)                    mm 2       1...25 strand
                                              u
                                                                                        1...35 cable
                                    Connections C  (63, 125 A)               mm 2       6...50 strand
                                              u
                                                                                        6...70 cable
                                    Tightening torque                        Nm         3.5
                                    Feed                                                any
                                    Mounting on DIN top hat rail                        EN 60715
                                    Permissible operating ambient temperature  °C       -25 ... +60
                                    Storage temperature                      °C         -40 ... +70
                                    Protection category                                 IP20
                                                                                        IP40 (actuating end only)
                                    Classification compliant to NF-16-101, NF16-102     I3, F2
                                    Vibration resistance                                IEC 60068-2-27; IEC 60068-2;
                                                                                        EN 61373 Cat.1/Class B


                                    Rated current             Internal resistance      Power loss
                                    I  [A]                    R  [mΩ]                  P  [W]
                                                              i
                                                                                        v
                                     n
                                       32                     1.7                      1.7
                                      63                      1.0                      4.0
                                    125                       0.6                      9.4