Page 427 - Din prodcuts 2020
P. 427

4/73




          —
          Auxiliary elements for S800
          S800-UVR



                                                                                                                       4
                                    S800-UVR
                                    Undervoltage release
                                    The S800-UVR undervoltage release can be used as an emergency-stop cut-as by use of
                                    suitable emergency stop buttons. The undervoltage release switches the power supply to
                                    the high performance MCB off in case of a failure or if the value falls below 0.7 x Un. After
                                    tripping, the high performance MCB can be switched back on as soon as the voltage is over
                                    0.85 x U .
                                          n
                                    Mounting ability of the S800-UVR undervoltage release
                                    The S800-UVR can be mounted by the user at the left side of the high performance MCB.



          Undervoltage release S800-UVR
                                            S800-UVR36       S800-UVR60       S800-UVR130      S800-UVR250
          Rated operational voltage U   e  VAC/DC  24 ... 36  48 ... 60       110 ... 130      220 ... 250
          Operating range
          open                      % U e   35 ... 70        35 ... 70        35 ... 70        35 ... 70
          closed                    % U e   85               85               85               85
          Rated insulation voltage U  V     690              690              690              690
                           i
          Power loss of coil when attracted  W/VA  1.11 ... 1.14/1.2*  1.14 ... 1.25/1.3*  1.3 ... 1.41/1.4*  1.71 ... 1.91/1.9*
          Rated frequency           Hz      DC; 50/60        DC; 50/60        DC; 50/60        DC; 50/60
          Pollution degree                  3                3                3                3
         Standard                           IEC 60947-2 / UL 489  IEC 60947-2 / UL 489  IEC 60947-2 / UL 489  IEC 60947-2 / UL 489
          Connection C  u           mm 2    1 ... 25 (14-2 AWG)   1 ... 25 (14-2 AWG)   1 ... 25 (14-2 AWG)   1 ... 25 (14-2 AWG)
                                            strand           strand           strand           strand
                                            1 ... 35 (14-3 AWG) cable 1 ... 35 (14-3 AWG) cable 1 ... 35 (14-3 AWG) cable 1 ... 35 (14-3 AWG) cable
          Tightening torque         Nm      3.5              3.5              3.5              3.5
          AC/DC supply                      any              any              any              any
         Mounting on DIN top hat rail       EN 60715         EN 60715         EN 60715         EN 60715
         Protection category                IP20             IP20             IP20             IP20
                                            IP40 (actuating end   IP40 (actuating end   IP40 (actuating end   IP40 (actuating end
                                            only)            only)            only)            only)
         Permissible operating ambient
         temperature                °C      -25 ... +60      -25 ... +60      -25 ... +60      -25 ... +60
         Storage temperature        °C      -40 ... +70      -40 ... +70      -40 ... +70      -40 ... +70
         Vibration resistance               IEC 60068-2-6; EN   IEC 60068-2-6; EN   IEC 60068-2-6; EN   IEC 60068-2-6; EN
                                            61373 Cat.1/Class B  61373 Cat.1/Class B  61373 Cat.1/Class B  61373 Cat.1/Class B





                                                           GTIN    Order details               Price  Weight Pack
                                                           761227                              1    1 piece unit

                                    Undervoltage release   EAN     Type code   Order code      piece  kg  pc.
                                    24...36 VAC/DC         1208363  S800-UVR36  2CCS800900R0241     0,15  1
                                    48...60 VAC/DC         1208370  S800-UVR60  2CCS800900R0251     0.15  1
                                    110...130 VAC/DC       1208387  S800-UVR130  2CCS800900R0261    0.15  1
                                    220...250 VAC/DC       1208394  S800-UVR250  2CCS800900R0271    0.15  1