Page 443 - Din prodcuts 2020
P. 443

4/89




          —
          Accessories for MCBs and RCDs
          Auxiliary switch S700 + H2WR



                                                                                                                       4
                            Auxiliary switch S700 + H2WR
                            2 Switch-over contacts
                            Conv. thermal current Ith  10 A
                            Min. operating voltage  24 V AC/DC
                            Min. switching power  5 VA a
                            Short-circuit withstand   1000 A @ 230 V AC with S 200 K6 back-up
                            capability
                            Isolation coordination
                               – overvoltage category  III
                               – pollution degree  2
                               – surge withstand   4 kV (1.2/50 µs)
                               capability
                            Wiring               up to 2 x 1.5 mm 2
                            Contact reliability under  5 g, 20 cycles 5…150…5 Hz
                                                 @ 24 V AC/DC, 5 mA
                                                 –> contact
                           a  The min. operating current under operating conditions acc. to EN 60204-1 and EN
                            60439-1 (indoor installation): 24 V AC/DC, 5 mA (AC 12, DC 12)


                            AC 14              Ue                  400 V              230V
                                               Ie                  2 A                6 A
                            DC 12              Ue                  220 V              110 V
                                               Ie                  1 A                1.5 A
                            DC 13              Ue                  60 V               24 V
                                               Ie                  2 A                4 A
   438   439   440   441   442   443   444   445   446   447   448