Page 454 - Din prodcuts 2020
P. 454

5/10             ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS   2CHC 420 001 C0201




          —
          Protection and safety
          OVR Type 1 surge protective devices




                                    Technical features
                                    Type codes                         OVR T1 25-255-7       OVR T1 3N 25-255-7
                                    with auxiliary contact (TS)        –                     –
  5
                                    Technology                         Spark-gap             Spark-gap + GDT
                                    Electrical features
                                    Standard                           IEC 61643-1/EN 61643-11   IEC 61643-1/EN 61643-11
                                    Type/test class                    T1/I                  T1/I
                                    Protected lines                    1                     3+1
         OVR T1 25-255-7            Types of networks                  TNC/TT(L-N)-TNS       TNS-TT
                                    Type of current                    AC 47-63 Hz           AC 47-63 Hz
                                    Voltage regulation of the system   ± 10 %                ± 10 %
                                    Nominal voltage Un           [V]   230                   230
                                    Maximum continuous operating   [V]  255                  255
                                    voltage Uc
                                    Maximum impulse current Iimp   [kA]  25                  25
                                    (10/350)
                                    Maximum impulse current Tot. Iimp   [kA]  25             100
                                    (10/350)
                                    Nominal discharge current In (8/20)  [kA]  25            25
                                    Follow current interrupting rating Ifi  [kA]  7          7
                                    Voltage protection level Up at In  [kV]  ≤ 2.5           2.0/2.0/2.0
                                    Voltage protection level Ures at 3 kA  [kV]  ≤ 0.9       0.9/0.9/0.9
                                    TOV (Temporary overvoltage)
                                    withstand Ut
                                                    (L-N: 5 s /N-PE:   [V]  650/–            650/1200
                                                    200 ms)
                                    Response time                [ns]  ≤ 100                 ≤ 100
                                    Residual current IPE         [µA]  10                    1000
                                    Short-circuit withstand      [kA]  50                    50
                                    capability Isccr
                                    Backup protection  Fuse (gG)  [A]  ≤ 125                 ≤ 125
                                                    Circuit breaker   [A]  ≤ 125             ≤ 125
                                                    (B or C curve)
                                    Pluggable cartridge                No                    No
                                    Integrated thermal disconnector    –                     –
                                    State indicator                    Yes                   Yes
                                    Safety reserve                     No                    No
                                    Auxiliary contact                  No                    No
                                    Installation
                                    Wire range      Solid wire   [mm²]  2.5…50               2.5…50
                                    (L, N, PE)      Stranded wire  [mm²]  2.5…35             2.5…35
                                    Stripping length (L, N, PE)  [mm]  15                    15
                                    Tightening torque (L, N, PE)  [Nm]  3.5                  3.5
                                    Auxiliary contact (TS)
                                    Contact complement                 –                     –
                                    Minimum load                       –                     –
                                    Maximum load                       –                     –
                                    Connection cross-section     [mm²]  –                    –
                                    Miscellaneous characteristics
                                    Stocking and operating temperature  [°C]  -40 to +80     -40 to +80
                                    Maximal Altitude             [m]   2000                  2000
                                    Degree of protection               IP20                  IP20
                                    Fire resistance according to UL 94  V-0                  V-0
                                    Dimensions      height x width x  [mm]  85 x 17.8 x 70.8  85 x 89 x 70.8
                                                    depth        [inches] 3.34 x 0.70 x 2.78  3.34 x 3.50 x 2.78
                                    Dimensions with   height x width x  [mm]  –              –
                                    auxiliary contact (TS) depth  [inches] –                 –
   449   450   451   452   453   454   455   456   457   458   459