Page 456 - Din prodcuts 2020
P. 456
5/12 ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS 2CHC 420 001 C0201
—
Protection and safety
OVR Type 1 surge protective devices Single pole neutral
Technical features
Type codes OVR T1 50 N
with auxiliary contact (TS) –
5
Technology Gas discharge tube (GDT)
Electrical features
Standard IEC 61643-1/EN 61643-11
Type/test class T1/I
Protected lines 1
OVR T1 50 N Types of networks TT (N-PE) / TNS (N-PE)
Type of current AC 47-63 Hz
Voltage regulation of the system ± 10 %
network
Nominal voltage Un [V] 230
Maximum continuous operating [V] 255
voltage Uc
Maximum impulse current Iimp [kA] 50
(10/350)
Maximum impulse current Tot. Iimp [kA] 50
(10/350)
Nominal discharge current In (8/20) [kA] 25
Follow current interrupting rating Ifi [kA] 0.1
Voltage protection level Up at In [kV] ≤ 1.5
Voltage protection level Ures at 3 kA [kV] 0.9
TOV (Temporary (L-N: 5 s /N-PE: [V] –/1200
overvoltage) 200 ms)
withstand Ut
Response time [ns] ≤ 100
Residual current IPE [µA] 10
Short-circuit withstand capability Isccr [kA] 50
Backup Fuse (gG) [A] –
protection
Circuit breaker [A] –
(B or C curve)
Pluggable cartridge No
Integrated thermal disconnector
State indicator No
Safety reserve No
Auxiliary contact No
Installation
Wire range (L, N, Solid wire [mm²] 2.5…50
PE)
Stranded wire [mm²] 2.5…35
Stripping length (L, N, PE) [mm] 15
Tightening torque (L, N, PE) [Nm] 3.5
Auxiliary contact (TS)
Contact complement –
Minimum load –
Maximum load –
Connection cross-section [mm²] –
Miscellaneous characteristics
Stocking and operating temperature [°C] -40 to +80
Maximal Altitude [m] 2000
Degree of protection IP20
Fire resistance according to UL 94 V-0
Dimensions height x width x [mm] 85 x 35.6 x 64.8
depth [inches] 3.35 x 1.40 x 2.55
with auxiliary height x width x [mm] –
contact (TS) depth [inches] –