          Protection and safety
          OVR surge protective devices – UL Version
          Selection tables


          Choosing the correct model                          Complete facility protection
                                                              Installing surge protection at the main distribution panel is
          1) Determine the service voltage                    only the beginning of protecting the entire operation. As
  5
          Consult qualified personnel if the facility or operation ser-  most transient surges are created internally, it is necessary
          vice voltage is unknown.                            to install surge protection at sub-distribution panels (equip-
                                                              ment protection) to be fully protected. Stepping down the
          2) Select the SPD maximum continuous operating voltage   Imax level from the service entrance panel toward equip-
          (MCOV, Uc)                                          ment to be protected is recommended.
          The MCOV should correspond to the service voltage.  For example, if a 40 kA Imax SPD is installed in the main dis-
          Example: If the service voltage is 480 V Delta, an SPD with   tribution panel, then 15 kA Imax SPDs should be installed in
          550 V or 660 V MCOV will be required.               sub-distribution panels for equipment protection.
          Surge protection devices must also provide a level of protec-
          tion compatible with the withstand voltage of the equip-  Coordination
          ment. This withstand voltage depends on the type of equip-  It may be necessary to add a second surge protector, wired
          ment and its sensitivity. The incoming surge protector may   to the incoming unit, to achieve the required voltage protec-
          not provide adequate protection by itself, as certain electri-  tion and/or surge capacity. For Type 2 or 4 SPDs, installing
          cal phenomena may greatly increase its residual voltage if   this second unit a minimum of 1 m from the first unit will al-
          cable lengths exceed 10 m. A second SPD may be necessary.   low the two to work together, achieving the required protec-
                                                              tion.
          3) Select the SPD surge capacity (Imax)
          Surge capacity is the amount of energy the SPD can with-  Wiring rules
          stand from a single surge event. The higher the surge capac-  The impedance of the cables increases the voltage across
          ity, the longer the device will protect the system. A second   the connected equipment. Therefore, the length of the cable
          surge protector may be required if the surge capacity of the   between the surge protector and the equipment should be
          first is not capable of diverting all surge current to ground.   minimized.
          See coordination below.                             The surge protective device should be installed as close to
                                                              the equipment to be protected as possible. If this is not pos-
          4) Remote monitoring (Optional)                     sible (the equipment is over 30 m from the panel), then
          Integrated auxiliary contact for remote monitoring available   a second surge protector must be installed.
          on models with "TS" designation. Consult "Selection tables"
          on next page for help in the selection of SPDs.


          Pro-  Impulse Max.    Nominal    Follow   Voltage  Nominal  Max. cont. Type           Order code
          tected   current  discharge  discharge  current   protection  voltage  operating
          lines        current  current  interrupting  Rating         voltage
                Iimp                    rating
                10/350  Imax 8/20  In   Ifi       VPR      Un         MCOV
                kA     kA       kA      kA        kV       V          V
          Type 2 - Pluggable - Single Pole networks
          1     –      15       5       –         0.6      120        150     OVR T2 15-150 P U  2CTB802341R0000
          1     –      15       5       –         1        277  ±15%  320     OVR T2 15-320 P U  2CTB802341R0400
          1     –      40       20      –         0.6      120        150     OVR T2 40-150 P U  2CTB802341R2000
          1     –      40       20      –         0.6      120        150     OVR T2 40-150 P TS U  2CTB802341R2100
          1     –      40       20      –         1        277  ±15%  320     OVR T2 40-320 P U  2CTB802341R2400
          1     –      40       20      –         1        277  ±15%  320     OVR T2 40-320 P TS U  2CTB802341R2500
          1     –      40       10      –         1.3      347  ±15%  440     OVR T2 40-440 P TS U  2CTB802341R2900
          1     –      40       10      –         1.7      480  ±15%  550     OVR T2 40-550 P TS U  2CTB802341R3300
          1     –      40       10      –         1.9      600  ±15%  660     OVR T2 40-660 P TS U  2CTB802341R3700
          Neutral
          1     –      70       20      0.1       1.2      230        275     OVR T2 70 N P U   2CTB802341R8000
          Cartridges
          1     –      –        –       –         –        120  ±15%  175     OVR T2 15-150 C U  2CTB802348R2500
          1     –      –        –       –         –        277  ±15%  320     OVR T2 15-320 C U  2CTB802348R2700
          1     –      –        –       –         –        120  ±15%  175     OVR T2 40-150 C U  2CTB802348R3500
          1     –      –        –       –         –        277  ±15%  320     OVR T2 40-320 C U  2CTB802348R3700
          1     –      –        –       –         –        347  ±15%  440     OVR T2 40-440 C U  2CTB802348R3900
          1     –      –        –       –         –        480  ±15%  550     OVR T2 40-550 C U  2CTB802348R4100
          1     –      –        –       –         –        600  ±15%  660     OVR T2 40-660 C U  2CTB802348R4300
          1     –      –        –       –         –        230        275     OVR T2 70 N C U   2CTB802348R6500