Page 525 - Din prodcuts 2020
P. 525

5/81




          —
          Protection and safety
          OVR Type 2 surge protective devices - Single phase networks








                                                                                                                       5
 General technical data
 Type  OVR T2 1N 15-150 P U  OVR T2 1N 15-320 P U  OVR T2 1N 40-150 P U  –  –  –      –
 with auxiliary contact (TS)  –  –  OVR T2 1N 40-150 P TS U  OVR T2 1N 40-320 P TS U  OVR T2 1N 40-440 P TS U  OVR T2 1N 40-550 P TS U  OVR T2 1N 40-660 P TS U
 Electrical features
 Standards  UL 1449  UL 1449  UL 1449  UL 1449  UL 1449      UL 1449                  UL 1449
 Type / test class (UL 1449)  4  4  4  4  4                  4                        4
 Protected lines  2  2  2  2       2                         2                        2
 Type of current / frequency  AC 47-63 Hz  AC 47-63 Hz  AC 47-63 Hz  AC 47-63 Hz  AC 47-63 Hz  AC 47-63 Hz  AC 47-63 Hz
 Voltage regulation of the system network  ±15%  ±15%  ±15%  ±15%  ±15%  ±15%         ±15%
 Nominal system voltage Un  120 V  277 V  120 V  277 V  347 V  480 V                  600 V
 Maximum continuous operating voltage MCOV  150 V  320 V  150 V  320 V  440 V  550 V  660 V
 Maximal discharge current (8/20) Imax  15 kA  15 kA  40 kA  40 kA  40 kA  40 kA      40 kA
 Nominal discharge current (8/20) In  5 kA  5 kA  20 kA  20 kA  10 kA  10 kA          10 kA
 Voltage protection rating (L-N / N-G / L-G) VPR  1.2 kV  1.2 kV  1.2 kV  1.2 kV  1.2 kV  1.2 kV  1.2 kV
 Response time  < 25 ns  < 25 ns  < 25 ns  < 25 ns  < 25 ns  < 25 ns                  < 25 ns
 Short circuit   SCCR  200 kA  200 kA  200 kA  200 kA  200 kA  200 kA                 200 kA
 withstand
 Back up protection   fuse (gG - gL)  ≤ 100 A  ≤ 100 A  ≤ 100 A  ≤ 100 A  ≤ 100 A  ≤ 100 A  ≤ 100 A
 maximum rating  circuit breaker (B or C curve) ≤ 125 A  ≤ 125 A  ≤ 125 A  ≤ 125 A  ≤ 125 A  ≤ 125 A  ≤ 125 A
 Pluggable cartridges  Yes  Yes  Yes  Yes  Yes               Yes                      Yes
 Integrated QuickSafe  technology  Yes  Yes  Yes  Yes  Yes   Yes                      Yes
 ®
 State indicator  Yes  Yes  Yes  Yes  Yes                    Yes                      Yes
 Safety reserve  –  –  –  –        –                         –                        –
 Auxiliary contact (TS)  No  No  Yes (TS option)  Yes  Yes   Yes                      Yes
 Installation
 Wire range (L,N,PE)  solid wire  2.5…25 / 4…14 mm²  2.5…25 / 4…14 mm²  2.5…25 / 4…14 mm²  2.5…25 / 4…14 mm²  2.5…25 / 4…14 mm²  2.5…25 / 4…14 mm²  2.5…25 / 4…14 mm²
 stranded wire  2.5…16 / 6…14 mm²  2.5…16 / 6…14 mm²  2.5…16 / 6…14 mm²  2.5…16 / 6…14 mm²  2.5…16 / 6…14 mm²  2.5…16 / 6…14 mm²  2.5…16 / 6…14 mm²
 Stripping length (L,N,PE)  12.5 / 0.5 mm  12.5 / 0.5 mm  12.5 / 0.5 mm  12.5 / 0.5 mm  12.5 / 0.5 mm  12.5 / 0.5 mm  12.5 / 0.5 mm
 Tightening torque (L,N,PE)  2.8 / 24.5 Nm  2.8 / 24.5 Nm  2.8 / 24.5 Nm  2.8 / 24.5 Nm  2.8 / 24.5 Nm  2.8 / 24.5 Nm  2.8 / 24.5 Nm
 Auxiliary contact (TS)
 Contact information  2 NO – 2 NC  2 NO – 2 NC  2 NO – 2 NC  2 NO – 2 NC              2 NO – 2 NC
 Min. load  12 V DC – 10 mA  12 V DC – 10 mA  12 V DC – 10 mA  12 V DC – 10 mA        12 V DC – 10 mA
 Max. load  250 V AC – 1 A  250 V AC – 1 A  250 V AC – 1 A   250 V AC – 1 A           250 V AC – 1 A
 Connection cross section  1.5 / 16 mm²  1.5 / 16 mm²  1.5 / 16 mm²  1.5 / 16 mm²     1.5 / 16 mm²
 Miscellaneous characteristics
 Stocking   -40...+80 °C  -40...+80 °C  -40...+80 °C  -40...+80 °C  -40...+80 °C  -40...+80 °C  -40...+80 °C
 temperature
 Maximal Altitude  5 000 m  5 000 m  5 000 m  5 000 m  5 000 m  5 000 m               5 000 m
 Operating   -40...+176 °C  -40...+176 °C  -40...+176 °C  -40...+176 °C  -40...+176 °C  -40...+176 °C  -40...+176 °C
 temperature
 Degree of protection  NEMA 1  NEMA 1  NEMA 1  NEMA 1  NEMA 1  NEMA 1                 NEMA 1
 Fire resistance according to UL 94  V0  V0  V0  V0  V0      V0                       V0
 Dimensions  mm  h x w x d 90.5 x 35.6 x 64.8 mm  90.5 x 35.6 x 64.8 mm  90.5 x 35.6 x 64.8 mm  –  –  –  –
 inches  h x w x d 3.56 x 1.4 x 2.55 in  3.56 x 1.4 x 2.55 in  3.56 x 1.4 x 2.55 in  –  –  –  –
 Dimensions with    mm  h x w x d –  –  98.5 x 35.6 x 64.8 mm  98.5 x 35.6 x 64.8 mm  98.5 x 35.6 x 64.8 mm  98.5 x 35.6 x 64.8 mm  98.5 x 35.6 x 64.8 mm
 auxiliary contact (TS)  inches  h x w x d –  –  3.88 x 1.4 x 2.55 in  3.88 x 1.4 x 2.55 in  3.88 x 1.4 x 2.55 in  3.88 x 1.4 x 2.55 in  3.88 x 1.4 x 2.55 in
 Replacement cartridges
 Phase product ID  Type  OVR T2 15-150 C U  OVR T2 15-320 C U  OVR T2 40-150 C U  OVR T2 40-320 C U  OVR T2 40-440 C U  OVR T2 40-550 C U  OVR T2 40-660 C U
 Order code  2CTB802348R2500  2CTB802348R2700  2CTB802348R3500  2CTB802348R3700  2CTB802348R3900  2CTB802348R4100  2CTB802348R4300
 Neutral product ID  Type  OVR T2 70 N C U  OVR T2 70 N C U  OVR T2 70 N C U  OVR T2 70 N C U  OVR T2 70 N C U  OVR T2 70 N C U  OVR T2 70 N C U
 Order code  2CTB802348R6500  2CTB802348R6500  2CTB802348R6500  2CTB802348R6500  2CTB802348R6500  2CTB802348R6500  2CTB802348R6500
   520   521   522   523   524   525   526   527   528   529   530