Page 527 - Din prodcuts 2020
P. 527

5/83




          —
          Protection and safety
          OVR Type 2 surge protective devices - Delta networks








                                                                                                                       5
          General technical data
            Type                               OVR T2 3L 15-320 P U  –                     –
            with auxiliary contact (TS)        –                     OVR T2 3L 40-320 P TS U  OVR T2 3L 40-550 P TS U
          Electrical features
            Standards                          UL 1449               UL 1449               UL 1449
            Type / test class (UL 1449)        1                     1                     1
            Protected lines                    3                     3                     3
            Type of current / frequency        AC 47-63 Hz           AC 47-63 Hz           AC 47-63 Hz
            Voltage regulation of the system network  ±15%           ±15%                  ±15%
            Nominal system voltage Un          277 V                 277 V                 480 V
            Maximum continuous operating voltage MCOV  320 V         320 V                 550 V
            Maximal discharge current (8/20) Imax  15 kA             40 kA                 40 kA
            Nominal discharge current (8/20) In  5 kA                20 kA                 10 kA
            Voltage protection rating (L-N / N-G / L-G) VPR  1 kV    1 kV                  1.7 kV
            Response time                      < 25 ns               < 25 ns               < 25 ns
            Short circuit   SCCR               200 kA                200 kA                200 kA
            withstand
            Back up protection  fuse (gG - gL)  ≤ 100 A              ≤ 100 A               ≤ 100 A
            maximum rating  circuit breaker (B or C curve)  ≤ 125 A  ≤ 125 A               ≤ 125 A
            Pluggable                          Yes                   Yes                   Yes
            cartridges
            Integrated QuickSafe  technology   Yes                   Yes                   Yes
                           ®
            State indicator                    Yes                   Yes                   Yes
            Safety reserve                     –                     –                     –
            Auxiliary contact                  No                    Yes                   Yes
            (TS)
          Installation
            Wire range (L,N,PE) solid wire     2.5…25 / 4…14 mm²     2.5…25 / 4…14 mm²     2.5…25 / 4…14 mm²
                           stranded wire       2.5…16 / 6…14 mm²     2.5…16 / 6…14 mm²     2.5…16 / 6…14 mm²
            Stripping length (L,N,PE)          12.5 / 0.5 mm         12.5 / 0.5 mm         12.5 / 0.5 mm
            Tightening torque (L,N,PE)         2.8 / 24.5 Nm         2.8 / 24.5 Nm         2.8 / 24.5 Nm
          Auxiliary contact (TS)
            Contact                            –                     3 NO – 3 NC           3 NO – 3 NC
            information
            Min. load                          –                     12 V DC – 10 mA       12 V DC – 10 mA
            Max. load                          –                     250 V AC – 1 A        250 V AC – 1 A
            Connection cross section           –                     1.5 / 16 mm²          1.5 / 16 mm²
          Miscellaneous characteristics
            Stocking temperature               -40...+80 °C          -40...+80 °C          -40...+80 °C
            Maximal Altitude                   5 000 m               5 000 m               5 000 m
            Operating temperature              -40...+176 °C         -40...+176 °C         -40...+176 °C
            Degree of                          NEMA 1                NEMA 1                NEMA 1
            protection
            Fire resistance according to UL 94  V0                   V0                    V0
            Dimensions     mm           h x w x d  90.5 x 53.4 x 64.8 mm  –                –
                           inches       h x w x d  3.56 x 2.1 x 2.55 in  –                 –
            Dimensions with    mm       h x w x d  –                 98.5 x 53.4 x 64.8 mm  98.5 x 53.4 x 64.8 mm
            auxiliary contact   inches  h x w x d  –                 3.88 x 2.1 x 2.55 in  3.88 x 2.1 x 2.55 in
            (TS)
          Replacement cartridges
            Phase product ID  Type             OVR T2 15-320 C U     OVR T2 40-320 C U     OVR T2 40-550 C U
                           Order code          2CTB802348R2700       2CTB802348R3700       2CTB802348R4100
            Neutral product ID  Type           –                     –                     –
                           Order code          –                     –                     –
   522   523   524   525   526   527   528   529   530   531   532