Page 526 - Din prodcuts 2020
P. 526

5/82             ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS   2CHC 420 001 C0201




          —
          Protection and safety
          OVR Type 2 surge protective devices - Delta networks




                           Description
                           Delta devices provide the protection required by the three phases of a Delta network system.
                           OVR T2 devices provide the best protection as they are designed to protect electric installations and
  5
                           sensitive equipment against indirect surges with ensuring a low protection level (VPR). They are char-
                           acterized by their capacity to safely discharge current with 8/20 μs wave form.


                           Ordering details
        OVR T2 3L 15-320 P U
                            Pro-  Max   Nominal Voltage Nominal  Max.  Bbn  Type            Order code    Weight
                            tected  dis-  dis-  protec-  voltage  cont.  3660308
                            lines  charge  charge  tion       operat-                                     Pkg
                                 current  current  rating     ing                                         (1 pce)
                                 Imax                         voltage
                                 8/20   In     VPR    Un      MCOV,
                                                              Uc
                                 kA     kA     kV     V       V     EAN                                   kg
                            Pluggable
                            3    15     5      1      277  ±15%  320  518644  OVR T2 3L 15-320 P U 2CTB802345R0400 0.36
                            3    40     20     1      277  ±15%  320  518668  OVR T2 3L 40-320 P   2CTB802345R2500 0.36
                                                                            TS U
                            3    40     10     1.7    480  ±15%  550  518682  OVR T2 3L 40-550 P   2CTB802345R3300 0.36
       OVR T2 3L 40-320 P TS U                                              TS U
   521   522   523   524   525   526   527   528   529   530   531