Page 531 - Din prodcuts 2020
P. 531
5/87
—
Protection and safety
OVR Type 2 surge protective devices - Split phase networks
5
General technical data
Type OVR T2 2L OVR T2 2L – – OVR T2 2N OVR T2 2N – – – – –
15-150 P U 15-320 P U 15-150 P U 15-320 P U
with auxiliary contact (TS) – – OVR T2 2L 40- OVR T2 2L 40- – – OVR T2 2N OVR T2 2N OVR T2 2N OVR T2 2N OVR T2 2N
150 P TS U 320 P TS U 40-150 P TS U 40-320 P TS U 40-440 P TS U 40-550 P TS U 40-660 P TS U
Electrical features
Standards UL 1449 UL 1449 UL 1449 UL 1449 UL 1449 UL 1449 UL 1449 UL 1449 UL 1449 UL 1449 UL 1449
Type / test class (UL 1449) 1 1 1 1 4 4 4 4 4 4 4
Protected lines 2 2 2 2 3 3 3 3 3 3 3
Type of current / frequency AC 47-63 Hz AC 47-63 Hz AC 47-63 Hz AC 47-63 Hz AC 47-63 Hz AC 47-63 Hz AC 47-63 Hz AC 47-63 Hz AC 47-63 Hz AC 47-63 Hz AC 47-63 Hz
Voltage regulation of the system network ±15% ±15% ±15% ±15% ±15% ±15% ±15% ±15% ±15% ±15% ±15%
Nominal system voltage Un 120 V 277 V 120 V 277 V 120 V 277 V 120 V 277 V 347 V 480 V 600 V
Maximum continuous operating voltage MCOV 175 V 320 V 175 V 320 V 175 V 320 V 175 V 320 V 440 V 550 V 660 V
Maximal discharge current (8/20) Imax 15 kA 15 kA 40 kA 40 kA 15 kA 15 kA 40 kA 40 kA 40 kA 40 kA 40 kA
Nominal discharge current (8/20) In 5 kA 5 kA 20 kA 20 kA 5 kA 5 kA 20 kA 20 kA 10 kA 10 kA 10 kA
Voltage protection rating (L-N / N-G / L-G) VPR 0.6 kV 1 kV 0.6 kV 1 kV 0.7 kV 1.1 kV 0.7 kV 1.1 kV 1.4 kV 1.8 kV 2 kV
Response time < 25 ns < 25 ns < 25 ns < 25 ns < 25 ns < 25 ns < 25 ns < 25 ns < 25 ns < 25 ns < 25 ns
Short circuit withstand SCCR 200 kA 200 kA 200 kA 200 kA 200 kA 200 kA 200 kA 200 kA 200 kA 200 kA 200 kA
Back up protection fuse (gG - gL) ≤ 100 A ≤ 100 A ≤ 100 A ≤ 100 A ≤ 100 A ≤ 100 A ≤ 100 A ≤ 100 A ≤ 100 A ≤ 100 A ≤ 100 A
maximum rating circuit breaker (B or C ≤ 125 A ≤ 125 A ≤ 125 A ≤ 125 A ≤ 125 A ≤ 125 A ≤ 125 A ≤ 125 A ≤ 125 A ≤ 125 A ≤ 125 A
curve)
Pluggable cartridges Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes
Integrated QuickSafe technology Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes
®
State indicator Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes
Safety reserve – – – – – – – – – – –
Auxiliary contact (TS) No No Yes Yes No No Yes Yes Yes Yes Yes
Installation
Wire range (L,N,PE) solid wire 2.5…25 / 4…14 2.5…25 / 4…14 2.5…25 / 4…14 2.5…25 / 4…14 2.5…25 / 4…14 2.5…25 / 4…14 mm² 2.5…25 / 4…14 mm² 2.5…25 / 4…14 mm² 2.5…25 / 4…14 mm² 2.5…25 / 4…14 mm² 2.5…25 / 4…14 mm²
mm² mm² mm² mm² mm²
stranded wire 2.5…16 / 6…14 2.5…16 / 6…14 2.5…16 / 6…14 2.5…16 / 6…14 2.5…16 / 6…14 2.5…16 / 6…14 mm² 2.5…16 / 6…14 mm² 2.5…16 / 6…14 mm² 2.5…16 / 6…14 mm² 2.5…16 / 6…14 mm² 2.5…16 / 6…14 mm²
mm² mm² mm² mm² mm²
Stripping length (L,N,PE) 12.5 / 0.5 12.5 / 0.5 12.5 / 0.5 12.5 / 0.5 12.5 / 0.5 12.5 / 0.5 12.5 / 0.5 12.5 / 0.5 12.5 / 0.5 12.5 / 0.5 12.5 / 0.5
Tightening torque (L,N,PE) 2.8 / 24.5 Nm 2.8 / 24.5 Nm 2.8 / 24.5 Nm 2.8 / 24.5 Nm 2.8 / 24.5 Nm 2.8 / 24.5 Nm 2.8 / 24.5 Nm 2.8 / 24.5 Nm 2.8 / 24.5 Nm 2.8 / 24.5 Nm 2.8 / 24.5 Nm
Auxiliary contact (TS)
Contact information – – 2 NO – 2 NC 2 NO – 2 NC – – 3 NO – 3 NC 3 NO – 3 NC 3 NO – 3 NC 3 NO – 3 NC 3 NO – 3 NC
Min. load – – 12 V DC – 10 mA 12 V DC – 10 mA – – 12 V DC – 10 mA 12 V DC – 10 mA 12 V DC – 10 mA 12 V DC – 10 mA 12 V DC – 10 mA
Max. load – – 250 V AC – 1 A 250 V AC – 1 A – – 250 V AC – 1 A 250 V AC – 1 A 250 V AC – 1 A 250 V AC – 1 A 250 V AC – 1 A
Connection cross section – – 1.5 / 16 mm² 1.5 / 16 mm² – – 1.5 / 16 mm² 1.5 / 16 mm² 1.5 / 16 mm² 1.5 / 16 mm² 1.5 / 16 mm²
Miscellaneous characteristics
Stocking temperature -40...+80 °C -40...+80 °C -40...+80 °C -40...+80 °C -40...+80 °C -40...+80 °C -40...+80 °C -40...+80 °C -40...+80 °C -40...+80 °C -40...+80 °C
Maximal Altitude 5 000 m 5 000 m 5 000 m 5 000 m 5 000 m 5 000 m 5 000 m 5 000 m 5 000 m 5 000 m 5 000 m
Operating temperature -40...+176 °C -40...+176 °C -40...+176 °C -40...+176 °C -40...+176 °C -40...+176 °C -40...+176 °C -40...+176 °C -40...+176 °C -40...+176 °C -40...+176 °C
Degree of protection NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1
Fire resistance according to UL 94 V0 V0 V0 V0 V0 V0 V0 V0 V0 V0 V0
Dimensions mm h x w x d 90.5 x 35.6 x 64.8 90.5 x 35.6 x 64.8 – – 90.5 x 53.4 x 64.8 90.5 x 53.4 x 64.8 mm – – – – –
mm mm mm
inches h x w x d 3.56 x 1.4 x 2.55 in 3.56 x 1.4 x 2.55 in – – 3.56 x 2.1 x 2.55 in 3.56 x 2.1 x 2.55 in – – – – –
Dimensions with mm h x w x d – – 98.5 x 35.6 x 64.8 98.5 x 35.6 x 64.8 – – 98.5 x 53.4 x 64.8 mm 98.5 x 53.4 x 64.8 mm 98.5 x 53.4 x 64.8 mm 98.5 x 53.4 x 64.8 mm 98.5 x 53.4 x 64.8 mm
auxiliary contact (TS) mm mm
inches h x w x d – – 3.88 x 1.4 x 2.55 in 3.88 x 1.4 x 2.55 in – – 3.88 x 2.1 x 2.55 in 3.88 x 2.1 x 2.55 in 3.88 x 2.1 x 2.55 in 3.88 x 2.1 x 2.55 in 3.88 x 2.1 x 2.55 in
Replacement cartridges – – – – – – 1 NO – 1 NC 1 NO – 1 NC 1 NO – 1 NC 1 NO – 1 NC 1 NO – 1 NC
Phase product ID Type OVR T2 15-150 C U OVR T2 15-320 C U OVR T2 40-150 C U OVR T2 40-320 C U OVR T2 15-150 C U OVR T2 15-320 C U OVR T2 40-150 C U OVR T2 40-320 C U OVR T2 40-440 C U OVR T2 40-550 C U OVR T2 40-660 C U
Order code 2CTB802348R2500 2CTB802348R2700 2CTB802348R3500 2CTB802348R3700 2CTB802348R2500 2CTB802348R2700 2CTB802348R3500 2CTB802348R3700 2CTB802348R3900 2CTB802348R4100 2CTB802348R4300
Neutral product ID Type – – – – OVR T2 70 N C U OVR T2 70 N C U OVR T2 70 N C U OVR T2 70 N C U OVR T2 70 N C U OVR T2 70 N C U OVR T2 70 N C U
Order code – – – – 2CTB802348R6500 2CTB802348R6500 2CTB802348R6500 2CTB802348R6500 2CTB802348R6500 2CTB802348R6500 2CTB802348R6500