5/166            ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS   2CHC 420 001 C0201




          —
          Protection and safety
          Electronic Protection Devices for use behind 24 V DC Switch Mode Power Supplies




                                    Operating data
                                    Operating voltage UB  24 V DC (18...32 V)
                                    Current rating IN  fixed current ratings: 0.5, 1, 2, 3, 4, 6, 8, 10, 12 A
  5
                                    Closed current I0  ON condition: typically 20...30 mA depending on signal output
                                    Staus indication by   multico-  Green  - unit is ON (S1 = ON)
                                    means of         lour LED       - load circuit/Power-is switched on MOSFET
          EPD
                                                             Orange  -  in the event of overload or short circuit until electronic
                                                                     disconnection
                                                             Red    - unit electronically disconnected
                                                                    - load circuit/Power-MOSFET OFF
                                                                    - undervoltage (UB < 8 V)
                                                                    - after switch-on till the end of the delay period
                                                             OFF    - manually switched off (S1 = OFF) or device is dead
                                                     potential-free auxiliary contact F
                                                     ON/OFF/condition of switch S1

                                    Load circuit
                                    Load output                     Power-MOSFET switching output (high slide switch)
                                    Overload disconnection          typically 1.1 x IN (1.05...1.35 x IN)
                                    Short-circuit current IK        active current limitation (see table 1)
                                    Trip time                       see time/current characteristics
                                    For electronic disconnection    typically 3 s at ILoad > 1.1 x IN
                                                                    typically 100 ms...3 s at ILoad > 1.8 x IN (or 1.5 x IN/1.3 x IN, )
                                    Temperature disconnection       internal temperature monitoring with electronic disconnection
                                    Low voltage monitoring load output   with hysteresis, no reset required: load »OFF« at UB< 8 V
                                    Starting delay tStart           typically 0.5 sec after every switch-on and after applying US
                                    Disconnection of load circuit   electronic disconnection
                                    Free-wheeling circuit           suitable external free-wheeling circuit to be used
                                                                    with inductive load
                                    Several load outputs must not be connected
                                    in parallel

                                    Signal output F
                                    Electrical data                 potential-free auxiliary contact max. 30 V DC/0.5 A,
                                                                    min. 10 V DC/10 mA
                                    ON condition LED green          voltage UB applied, switch S1 is in ON position no overload,
                                                                    no short circuit
                                    OFF condition LED off           device switched off (switch S1 is in OFF position)
                                                                    no voltage UB applied
                                    Fault condition LED orange      overload condition > 1.1 x IN up to electronic disconnection
                                    Aux. contact                    single signal, make contact
                                                                    contact open, terminal 13-14
                                    Fault                           signal output fault conditions
                                                                    - no operating voltage UB
                                                                    - ON/OFF switch S1 is in OFF position
                                                                    - red LED lighted (electronic discon nection)