          E 236 undervoltage monitoring relays






                                    Technical features
                                                                                                                       5
                                                                     US 1.1     US 2.1     US 1.1D
                                    Supply circuit
                                    Supply voltage (= measured  voltage)  3N~ 400/230 V AC (terminals N-C1-C2-C3)
                                    Overvoltage permanent            3N~ 459/265 V AC
                                    Rated frequency                  48 – 63 Hz (AC sinus)
                                    Rated surge voltage:             4 kV
                                    Overvoltage category             III
          E 236                     Output circuit (isolated two-way-switch)
                                    Rated voltage                    250 V AC
                                    Switiching capacity              1250 VA (5 A/250 V AC)
                                    Continuous current               1250 VA (5 A/250 V AC)
                                    Fuse protection                  5 A flink
                                    Serviceable life, mechanical     15x106 switchover cycles
                                    Serviceable life, electric       2x105 switchover cycles at 1.000 VA resistive load
                                    Max. switching rate              max. 6/min at 1.000 VA resistive load
                                                                     max. 60/min at 100 VA resistive load
                                    Trip delay                       ca. 200 ms
                                    Pick-up delay (US 1.1D)          0.1 – 10 min
                                    Accuracy under constant conditions    ≤ 5 % of full scale value
                                    – setting accuracy (US 2.1/1.1D)  ≤ 2 %
                                    – repeat accuracy
                                    – temperature effect             ≤ 1 %
                                    Ambient temperature              – 25° to + 55 °C
                                    Terminals                        1 x 0.5 to 2.5 mm² with/without connector sleeve
                                                                     1 x 4 mm² without connector sleeve
                                                                     2 x 0.5 to 1.5 mm² with/without connector sleeve
                                                                     2 x 2.5 mm² without connector sleeve
                                    Pick-up torque                   max. 1 Nm
                                    Mounting position                optional
                                    Vibration resistance             10 to 55 Hz 0.35 mm (IEC 68-2-6)
                                    Shock resistance                 15 g 11 ms (IEC 68-2-27)
                                    Reference standards              VDE 0110 und VDE 0435
                                    EMC tests                        EN 61000-6-2 and EN 61000-6-4
                                    Back-up fuse                     ≤ 16 A
                                    Displays     green LED U/t ON    all 3 voltages ok
                                                 green LED U/t flashes  time-out indication
                                                 yellow LED ON/OFF   position of output relay

                                    All measured inputs have to be connected to one phase each. If no three-phase measure-
                                    ment should be carried out, measured inputs have to be connected to one phase to apply the
                                    required voltage to all measured inputs. If a load causes inverse voltage exceeding the
                                    threshold value Us, phase failures cannot be identified.
                                    A neutral conductor must be connected in any case!