5/172            ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS   2CHC 420 001 C0201




          —
          Protection and safety
          E 236 undervoltage monitoring relays





                                    Devices for panel installation onto mounting rails (35 mm) according to DIN EN 60715
                                    mounting depth:  68 mm
                                    mounting width:  17.5 mm = 1 module
  5
                                    color:         gray, RAL 7035
                                    Application - devices with 1CO contact
                                    For three-phase undervoltage monitoring (each phase connected to a neutral conductor)
                                    of switchgear. Devices with fixed threshold value (US 1.x and US 1.1 D) also for installations
                                    according to
                                    DIN VDE 0100-718 (for medical purposes) and DIN VDE 0108-100 (power installations and
          E 236-US 1.1              safety supply in installations for gathering of people).
                                    US 1.1:  3 phases to neutral conductor with fixed threshold value at 195 V; hysteresis fixed
                                           at 5 %
                                    US 2.1:   3 phases to neutral conductor with threshold value range of 160 – 240 V; hysteresis
                                           fixed at 5 %
                                    US 1.1D:    3 phases to neutral conductor with fixed threshold value at 195 V; hysteresis fixed
                                           at 5 %, but with switch-on delay of 0.1 (6 sec.) to 10 min

                                    Undervoltage monitoring device with pick-up delay E 236-US 1.1D
                                    If the measurement of the voltage of all phases connected exceeds the switching threshold
                                    U , including the hysteresis, the time delay (t) starts to run and the (green LED U/t) flashes.
                                     s
                                    Upon expiry of the time delay (t), the output relay R picks up (yellow LED on, green LED U/t
                                    flashes). If the measured voltage of one of the connected phases falls below the switching
                                    threshold U , the output relay de-energizes (yellow LED is off, green LED U/t is off).
          E 236-US 2.1                       s
                                    Contact              Bbn     Order details                Price  Weight  Pack
                                                         4016779                              1     1 piece  unit
                                                                                              piece
                                                         EAN     Type code     Order code           kg     pc.
                                    1 two-way switch     651776   E 236-US 1.1   2CDE165001R2001    0.05   10
                                    1 two-way switch     651783   E 236-US 2.1   2CDE165011R2001    0.05   10
                                    1 two-way switch     651790  E 236-US 1.1D  2CDE165001R2011     0.05   10