Page 617 - Din prodcuts 2020
P. 617

5/173




          —
          Protection and safety
          ISL industrial insulation monitoring devices




                                    Technical features ISL-A
                                                             ISL-A
                                                             A 24-48          A 115 and A 230  A 600                   5
                                    Power consumption   [VA]  3               4                6
                                    ALARM threshold     [kW]  30 - 300 (5 levels, selectable)
                                    TRIP threshold      [kW]  10 - 60         10 - 100         30 - 300 (adjustable by
                                                             (5 levels by switches)  (5 levels selectable)  potentiometer)
         ISL                        LED        ON            ■                ■                ■
                                    indications
                                               TRIP          ■                ■                ■
                                               ALARM                          ■
                                               +/-           ■                ■                ■
                                    Max trip delay      [s]  0.2              2                2.5
                                    Max measuring current  [mA]  0.5          1.8              1.5
                                    Internal impedance  [kW]  50              ISL-A 115: 200 kΩ   880 kW L+/L - 450 kW
                                                                              L+/L- 100 kΩ L/PE  L/PE
                                                                              ISL-A 230: 400 kΩ
                                                                              L+/L- 200 kΩ L/PE
                                    TRIP relay output        1 NO-C-NC        2 NO-C-NC        1 NO-C-NC
                                    ALARM relay output       2 NO-C-NC
                                    Relay contact capacity   max 250 V, 5 A
                                    Programmed   Alarm       ■
                                    functions  output
                                               Fail safe     ■
                                               Reset         ■
                                    Insulation               2.5 kV60 sec./   2.5 kV 60 sec./  2.5 kV 60 sec./
                                                             6 kV imp 1.2/50 μs  4 kV imp 1.2/50 μs  6 kV imp 1.2/50 μs
                                    Operating temperature  [°C]  -10 ÷ 60
                                    Storage temperature  [°C]  -20 ÷ 70
                                    Relative humidity        ≤ 90%
                                    Max terminal        [mm ]  4              2.5              2.5
                                                           2
                                    cross-section
                                    Protection degree        IP40 front, IP20 enclosure
                                    Modules             [n°]  3               6                6
                                    Weight              [g]  200              400              400
                                    Reference standards      EN 61010-1, EN 61557-8, EN 61326-1