          Command and signaling
          SD 200 and SHD 200 switch disconnector ranges












          Series                           SD 200                  SHD 200                 E 200                       6
          Standards and approvals          IEC/EN 60947-3          IEC/EN 60947-3          IEC/EN 60947-3
                                           VDE/CCC/EAC/KEMA        VDE/CCC/EAC/KEMA        VDE/CCC/KEMA
          Rated currents      16...63   [A]  16/25/32/40/50/63     16/25/32/40/50/63       –
                             80...125      –                       –                       80/100/125
          Rated voltage               [V AC] 253/440               240/415                 240/415
          Short circuit withstand capacity  [kA]  25               10                      80...100 A : 25; 125 A : 6
          Utilization category             AC-23A                  AC-22A                  AC-22A
          Electrical lifetime         [Ops.] I  < 32 A: 20,000 (AC)  I  < 32 A: 20,000 (AC)  I  < 100 A: 1,500 (AC)
                                            e
                                                                    e
                                                                                            e
                                           I  ≥ 32 A: 10,000 (AC)  I  ≥ 32 A: 10,000 (AC)  I  ≥ 125 A: 1,000 (AC)
                                            e                       e                       e
          Terminal cross section      [mm ] 35                     25                      50
                                         2
          Terminal                         Cylinder lift terminal  Cage terminal           Cage terminal
               Two terminal openings for
                conductor and busbar       Yes                     No                      No
             Safety wire guard             Yes                     No                      No
          Contact position indication      Marking on toggle (I ON/0 OFF)  Marking on toggle (I ON/0 OFF)  Marking on toggle (I ON/0 OFF)
                                           Real CPI (red ON/green OFF)
          Combination with auxiliary elements
                Auxiliary contacts         Right side              No                      Right side
                                           Left side
                                           Bottom side
                Shunt trip                 Yes                     No                      No

             Undervoltage release          Yes                     No                      No
             Motor operated remote control  Yes                    No                      No
             Padlock                       Yes                     Yes                     Yes
          Removal without disassembling of the   Yes               No                      Yes
          busbar