Page 638 - Din prodcuts 2020
P. 638

6/6              ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS   2CHC 420 001 C0201




          —
          Command and signaling
          SD 200 switch disconnector




                                    Technical data
                                    Electrical data
                                    Standards                               IEC/EN 60947-3
                                    Poles                                   1P, 2P, 3P, 4P
                                    Rated current I                         16 A, 25 A, 32 A, 40 A, 50 A, 63 A
                                              e
                                    Utilization category                    AC-23A, DC-21A
  6
                                    Rated voltage U                         1P: 253 V AC, 60 V DC
                                               e
          SD 201                                                            2P: 440 V AC, 125 V DC
                                                                            3…4P: 440 V AC
                                    Insulation voltage U i                  440 V AC
                                    Max. power frequency recovery voltage U  1P: 266 V AC, 63 V DC
                                                                max
                                                                            2P: 462 V AC, 131 V DC
                                                                            3…4P: 462 V AC
                                    Min. operating voltage U                12 V AC
                                                     Bmin.
                                    Rated frequency f                       50/60 Hz, DC
                                    Suitable for isolation                  Yes
                                    Rated conditional short-circuit current  25 kA in series with NH 00 ≤ 63 A gG
                                    Overvoltage category                    III
                                    Pollution degree                        3
                                    Rated impulse withstand voltage U imp.  (1.2/50 µs)   4 kV (test voltage 6.2 kV at sea level; 5 kV at 2,000 m)
                                    Dielectric test voltage                 2 kV (50/60 Hz, 1 min.)
                                    Mechanical data
                                    Housing                                 Insulation group I, RAL 7035
                                    Toggle                                  Insulation group II, red, sealable
                                    Contact position indication             Marking on toggle, I ON / 0 OFF
                                                                            Real CPI (green OFF/red ON)
                                    Protection degree acc. to EN 60529      IP20 / IP40 in enclosure with cover
                                    Electrical endurance                    I  < 32 A: 20,000 ops. (AC), 1,500 ops. (DC)
                                                                            e
                                                                            I  ≥ 32 A: 10,000 ops. (AC), 1,500 ops. (DC)
                                                                            e
                                    Mechanical endurance                    20,000  ops.
                                    Shock resistance acc. to IEC/EN 60068-2-27  25g, 2 shocks, 13 ms
                                    Vibration resistance acc. to IEC/EN 60068-2-6  5g, 20 cycles at 5…150…5 Hz with load 0.8 I n
                                    Environmental conditions (damp heat cyclic)   28 cycles with 55 °C/90-96% and 25 °C/95-100%
                                    acc. to IEC/EN 60068-2-30               [°C/RH]
                                    Ambient temperature                     -25 ... +55 °C
                                    Storage temperature                     -40 ... +70 °C
                                    Installation
                                    Terminal                                Cylinder lift terminal
                                              Safety wire guard             Yes
                                              Two terminal openings for conductor   Yes
                                              and busbar
                                    Cross-section of conductors             35 mm   2
                                    Cross-section of busbars                10 mm   2
                                    Torque                                  2.8 Nm
                                    Screwdriver                             No. 2 Pozidriv
                                    Mounting                                On DIN rail 35 mm acc. to EN 60715 by fast clip
                                    Mounting position                       Optional
                                    Removal without disassembling of the busbar  Yes
                                    Supply                                  Optional