          Control and automation
          E 450 priority switches




                                    Technical characteristics
                                                                      E 451-5.7             E 452-5.7
                                    Operating coil
                                    Range of rated current equivalent to  6.7 … 39 A
                                                                      correlates
                                                                      1.5 … 9 kW at 230 V, 4.6 … 27 kW at 230/400 V
                                    Threshold current                 3.1 … 5.3 A
                                    OFF delay (max.)                  0 main half waves     2 main half waves
                                    Max. continuous current           43 A
         E 450
                                    Therm. continuous capacity at 40 °C/104 °F  5 W
  7
                                    Contact assembly
                                    Control contact                   1 NC contact
                                    Rated contact current at 250 V    1 A
                                    Contact material                  solid silver
                                    Max. switching voltage            400 V
                                    Max. switching capacity           230 VA
                                    Max. switched current             1 A
                                    Max. inrush current peak          5 A
                                    Electr. service life              > 10  operations
                                                                         5
                                    Mechanical service life           app. 2 x 10  operations
                                                                             6
                                    Max. electrical switching rate    app. 1800 operations/hour
                                    ON duration                       100 %
                                    Ambient temperature               – 20 °C/– 4 °F to + 40 °C/104 °F
                                    Response time                     10 … 20 ms
                                    Release time                      5 … 20 ms             ≥ 20 ms
                                    Test voltage contact/coil         2.5 kV
                                    Clearance and creepage distance   C/250 V AC cording to IEC 669-1-23
                                    Protection degree                 IP 40
                                    Protection against electric shock  according to DIN VDE 0106 Part 100 (BGV A2)
                                                                                     2
                                    Terminal contact                  series coil up to 16 mm , control contact up to 2.5 mm 2
                                    E 450 priority switches
                                    The priority switch is used in wiring systems where existing lead cross sections or the size
                                    of the power supply service box do not allow for simultaneous operation of two powerful
                                    loads (e.g. storage heating and flow-type heater).
                                    The priority switch disconnects the long-term load (storage heating) for as long as the
                                    short-term consumer (flow-type heater) is switched on.
                                    The coil of the priority switch is connected in series to the short-term load. When this load is
                                    switched on, the NC contact of the priority switch disconnects e.g. the heating system
                                    contactor.

                                    For pneumatically controlled flow-type heaters
                                    Rated current   Power loss  Bbn  Order details            Price  Weight  Pack
                                    range                   4016779                           1    1 piece  unit

                                                W           EAN    Type code   Order code     piece kg     pc.
                                    6,7 ... 39 A  2.4       41590 3  E 451- 5.7 A  2CDE160000R0901  0.1    10

                                    For electronically controlled flow-type heaters
                                    Rated current   Power loss  Bbn  Order details            Price  Weight  Pack
                                    range                   4016779                           1    1 piece  unit

                                                W           EAN    Type code   Order code     piece  kg    pc.
                                     6.7 ... 39 A  2.4      20950 2  E 452-5.7 A  2CDE160010R0901  0.1     10