Page 739 - Din prodcuts 2020
P. 739

7/23




          —
          Control and automation
          E 235 mains disconnection relays




                                    E 235 Mains disconnection relay

                                    Application and method of operation
                                    According to building biologists, electrical interference fields emitted from live cables can
                                    impair well-being when the human organism is exposed to them for longer periods, e.g. in
                                    the bedroom. The E 235 demand switch automatically cuts off the mains voltage of an elec-
                                    tric circuit when the last consumer in that circuit has been switched off. When the first con-
                                    sumer is switched on, the device switches the mains voltage back on with almost no delay.
                                    A low voltage of approx. 3 V is used to monitor whether consumers are switched on. As alter-
          E 235-NFS                 nating voltage is used for this, it is virtually certain that even small consumer units with    7
                                    a capacitor and transformer power pack - e.g. charging stations for rechargeable devices,
                                    standard lamps, etc. - will be reliably detected and switched. Interference fields emitted by
                                    the monitoring voltage are so small that they cannot be registered. The mains is switched on
                                    when the consumer load exceeds the making capacity set in the demand switch. It is cut off
                                    when the consumer load falls to 2/3 of the set making capacity. The ON state is indicated by
                                    the integrated LED. You can choose between „Automatic monitoring“ and „Permanent ON“
                                    using a rotary switch on the E 235.

                                    Accessories
                                    The E 235-GLA base load adapter is also available, and is used for switching the demand
                                    switch on manually. The adapter is plugged into a socket that is monitored by the demand
         E 235-GLE                  switch. The toggle switch switches the base load, which is used to switch on the demand
                                    switch.
                                    Some consumers require an initial voltage equal to the mains voltage in order to be switched
                                    on. These include brightness controllers, and fluorescent and energy-saving lamps. The PTC
                                    base load element E 235-GLE and base load adapter E 235-GLA are available for ensuring reli-
                                    able switch-on of the mains field relay. The indicator light on the adapter displays the
                                    switched on mains voltage, irrespective of the position of the toggle switch. It tells you
                                    whether the mains voltage has been cut off or whether other consumers are still switched
                                    on. If you wish to connect a dimmer to the output of the demand switch, this must feature
                                    an additional switching contact. A base load element is also switched in parallel.



                                    Description           Bbn     Order details               Price  Weight  Pack
                                                          4016779                             1    1 piece  unit

                                                          EAN     Type code   Order code      piece  kg    pc.
                                    mains disconnection relay  571821   E 235-NFS   2CDE110000R1701   0.065   1
                                    base load element     571814   E 235-GLE   2CDE100500R1711     0.001   1
                                    base load adapter     571869   E 235-GLA   2CDE100510R1711     0.070   1