8/54             ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS   2CHC 420 001 C0201



          —
          Energy efficiency

          String monitoring CMS-660




                                            Circuit monitoring system for PV applications
                                            The CMS string monitoring increases the efficiency of photovoltaic systems
                                            by detecting failures on PV strings. With the easy-to-integrate system you can im-
                                            mediately detect unusual system status, e.g. defective strings, over-voltages,
                                            breaker trips or high temperatures, enabling you to quickly implement
                                            appropriate countermeasures.
               String
                                            Key features:
                                            •  Current and temperature measurement directly from the sensors
                                            •  Monitoring of two strings can be combined into one single CMS solid-core sensor
                                 Inverter   •  Integration of SPD and Switch disconnector status via 2 digital inputs
                                            •  Up to 32 flexible monitoring points, placed where measurement is required
                                            •  LEDs provide local information about network and device status.
  8
                                            •  Modbus RTU protocol guarantees easy integration into plant or inverter moni-
                                              toring systems
                                            •  Connection technology is extremely simple and requires no special tools
                          Combiner
                                            Control unit – CMS-660
                                            Main technical specification                                 CMS-660
                                            General data
                                            Degree of protection                                            IP20
                                            Operating temperature                  [°C]                − 25 .. +70 °C
                                            Storage temperature                    [°C]               − 40 .. +85 °C
                                            Dimensions W / H / D                  [mm]      71.8 x 87.0 x 64.9 (4 modules)
                                            Screw-type terminals                              0.5…2.5 mm², max 0.6 Nm
                                            Altitude                                [m]                  ≤ 2000 m
                                            Insulation strength                   [VAC]                     400
                                            Installation on DIN-rail                            35 mm (DIN EN 50022)
                                            Reference standards                         IEC 61010-1 UL | 508/CSA C22.2 No. 14
                                            Supply
                                            Supply voltage                        [VDC]                 24 (±10%)
                                            Power Input                             [W]     0.5 - 11 (dep. on n. of sensors)
                                            Serial interface (RS-485)
                                            Serial transmission speed                               2.4 … 115. 2 kbps
                                            Cable type                                             Twisted, shielded
                                            Communication protocol                                     Modbus RTU
                                            Measuring inputs
                                            Max. number of sensors                                           32
                                            Refresh time                                     ≤1 sec with max 32 sensors
                                            Digital inputs                                                    2
                                            Connection method                                 Push-in spring connection
                                            Cable diameter                                            max. 0.5mm²
                                            Electrical characteristics                        for potential-free contact
                                            Micro USB port                                                    1




                                            Control Unit
                                                            Description                   Weight of 1   Unit conf.
                                                            Type      ABB code            unit (kg)   (Pcs)
                                            CMS-660 control unit  CMS-660  2CCA880020R0001  0.153     1