Solid-core sensors 25 mm
Sensor type CMS-200xx CMS-201xx CMS-202xx
Measurement range [A] 160 80 40
Measurement method TRMS, AC 50 / 60 Hz, DC
CMS-120PS Peak value of the distorted wave-form ≤ 1.5 ≤ 3 ≤ 6
AC accuracy (TA = +25°C)* ≤ ± 0.5 %
AC* temperature coefficient ≤ ± 0.036 %
AC accuracy (TA = +25°C)* ≤ ± 0.7 % ≤ ± 1.0 % ≤ ± 1.7 %
DC* temperature coefficient ≤ ± 0.047 % ≤ ± 0.059 % ≤ ± 0.084 %
Resolution [A] 0.01
CMS-120DR Internal sampling rate [Hz] 5000 8
Respond time (±1 %) [sec] Type 0.25
Max. diameter of the cable [mm] 15
Insulation [V] 690 V AC /1500 V DC
Operating temperature [°C] − 25 ... +70 / − 40 ... + 85
Size CMS-200S8 series [mm] 26.5 x 43.0 x 38.5
CMS-200DR series [mm] 25.4 x 43.0 x 43.2
CMS-120CA
CMS-200CA series [mm] 25.4 x 43.0 x 35.7
Reference standard IEC 61010-1 | UL508 / CSA C22.2 No 14