Page 789 - Din prodcuts 2020
P. 789

8/49















                           Solid-core sensors 25 mm

                           Sensor type                               CMS-200xx     CMS-201xx     CMS-202xx
                           Measurement range                   [A]   160           80            40
                           Measurement method                        TRMS, AC 50 / 60 Hz, DC
          CMS-120PS        Peak value of the distorted wave-form     ≤ 1.5         ≤ 3           ≤ 6
                           AC accuracy (TA = +25°C)*                 ≤ ± 0.5 %
                           AC* temperature coefficient               ≤ ± 0.036 %
                           AC accuracy (TA = +25°C)*                 ≤ ± 0.7 %     ≤ ± 1.0 %     ≤ ± 1.7 %
                           DC* temperature coefficient               ≤ ± 0.047 %   ≤ ± 0.059 %   ≤ ± 0.084 %
                           Resolution                          [A]   0.01
          CMS-120DR        Internal sampling rate              [Hz]  5000                                              8
                           Respond time (±1 %)                 [sec]  Type 0.25
                           Max. diameter of the cable          [mm]  15
                           Insulation                          [V]   690 V AC /1500 V DC
                           Operating temperature               [°C]  − 25 ... +70 / − 40 ... + 85
                           Size        CMS-200S8 series        [mm]  26.5 x 43.0 x 38.5
                                       CMS-200DR series        [mm]  25.4 x 43.0 x 43.2
          CMS-120CA
                                       CMS-200CA series        [mm]  25.4 x 43.0 x 35.7
                           Reference standard                        IEC 61010-1 | UL508 / CSA C22.2 No 14
                           * All accuracy specifications refer to the relevant full scale value and apply at 25 °C.
   784   785   786   787   788   789   790   791   792   793   794