24 EASYLINE XLP FUSE SWITCH DISCONNECTOR 1-2-3- 4 POLES
—
Technical data
—
XLP 1-pole
XLP00 XLP1 XLP2 XLP3
For NH fuse links acc. to IEC60269-2-1 NH000/NH00 NH1 NH2 NH3
Rated operational voltage Ue AC (V) - 500 690 - 500 690 - 500 690 - 500 690
Rated operational voltage Ue DC (V) 220 - - 220 - - 220 - - 220 - -
Rated operational current Ie (A) 160 160 125 250 250 200 400 400 315 630 630 500
Thermal current with fuse-link Ith (A) 160 160 160 250 250 250 400 400 - 630 630 -
Utilization category DC22B AC22B AC21B DC22B AC22B AC21B DC22B AC22B AC21B DC22B AC22B AC21B
Rated insulation voltage Ui (V) 1000 1000 1000 1000
Rated impulse withstand voltage Uimp (kV) 8 8 8 8
Rated conditional short circuit current (kArms) 50 50 50 50
Rated frequency (Hz) 50 - 60 50 - 60 50 - 60 50 - 60
Power loss (Ith) without fuselink,
per phase (W) 3,5 7,5 13 24
Electrical durability 200 200 200 200
Mechanical durability 1400 1400 800 800
Degree of protection from the front Open IP20 IP20 IP20 IP20
according to IEC60529
Closed IP30 IP30 IP30 IP30
—
XLP 2-pole
XLP00 XLP1 XLP2 XLP3
For NH fuse links acc. to IEC60269-2-1 NH000/NH00 NH1 NH2 NH3
Rated operational voltage Ue AC (V) - 500 690 - 500 690 - 500 690 - 500 690
Rated operational voltage Ue DC (V) 220 - - 440 - - 440 - - 440 - -
Rated operational current Ie (A) 160 160 125 250 250 200 400 400 315 630 630 500
Thermal current with fuse-link Ith (A) 160 160 160 250 250 250 400 400 - 630 630 -
Utilization category DC22B AC22B AC21B DC22B AC22B AC21B DC22B AC22B AC21B DC22B AC22B AC21B
Rated insulation voltage Ui (V) 1000 1000 1000 1000
Rated impulse withstand voltage Uimp (kV) 8 8 8 8
Rated conditional short circuit current (kArms) 50 50 50 50
Rated frequency (Hz) 50 - 60 50 - 60 50 - 60 50 - 60
Power loss (Ith) without fuselink,
per phase (W) 3,5 7,5 13 24
Electrical durability 200 200 200 200
Mechanical durability 1400 1400 800 800
Open IP20 IP20 IP20 IP20
Degree of protection from the front
according to IEC60529 Closed IP30 IP30 IP30 IP30