Page 24 - DIN Disconnectors
P. 24

24               EASYLINE XLP FUSE SWITCH DISCONNECTOR 1-2-3- 4 POLES



          —

          Technical data











          —
          XLP 1-pole
                                                  XLP00            XLP1             XLP2             XLP3
          For NH fuse links acc. to IEC60269-2-1  NH000/NH00       NH1              NH2              NH3
          Rated operational voltage Ue   AC  (V)  -  500  690  -   500   690    -   500   690    -   500   690
          Rated operational voltage Ue DC  (V)  220  -   -    220    -    -    220    -    -    220    -    -
          Rated operational current Ie  (A)  160   160  125   250   250  200   400  400   315   630   630  500
          Thermal current with fuse-link Ith  (A)  160  160  160  250  250  250  400  400  -    630   630   -
          Utilization category              DC22B AC22B  AC21B  DC22B AC22B  AC21B  DC22B AC22B  AC21B  DC22B AC22B  AC21B
          Rated insulation voltage  Ui  (V)       1000             1000             1000             1000
          Rated impulse withstand voltage Uimp  (kV)  8             8                8                8
          Rated conditional short circuit current  (kArms)  50      50               50               50
          Rated frequency             (Hz)       50 - 60           50 - 60          50 - 60          50 - 60
          Power loss (Ith) without fuselink,
          per phase                   (W)          3,5                7,5              13             24
          Electrical durability                    200             200               200              200
          Mechanical durability                   1400             1400             800              800
          Degree of protection from the front           Open  IP20  IP20            IP20             IP20
          according to IEC60529
                                      Closed      IP30             IP30             IP30             IP30

          —
          XLP 2-pole
                                                  XLP00            XLP1             XLP2             XLP3
          For NH fuse links acc. to IEC60269-2-1  NH000/NH00       NH1              NH2              NH3
          Rated operational voltage Ue AC  (V)  -  500  690    -   500   690    -   500   690    -   500   690
          Rated operational voltage Ue DC  (V)  220  -   -    440    -    -    440    -    -    440    -    -
          Rated operational current Ie  (A)  160   160  125   250   250  200   400  400   315   630   630  500
          Thermal current with fuse-link Ith  (A)  160  160  160  250  250  250  400  400  -    630   630   -
          Utilization category              DC22B AC22B  AC21B  DC22B AC22B  AC21B  DC22B AC22B  AC21B  DC22B AC22B  AC21B
          Rated insulation voltage  Ui  (V)       1000             1000             1000             1000
          Rated impulse withstand voltage Uimp  (kV)  8             8                8                8
          Rated conditional short circuit current  (kArms)  50      50               50               50
          Rated frequency             (Hz)       50 - 60           50 - 60          50 - 60          50 - 60
          Power loss (Ith) without fuselink,
          per phase                   (W)          3,5              7,5              13               24
          Electrical durability                    200             200               200              200
          Mechanical durability                   1400             1400             800              800
                                      Open        IP20             IP20             IP20             IP20
          Degree of protection from the front
          according to IEC60529       Closed      IP30             IP30             IP30             IP30
   19   20   21   22   23   24   25   26   27   28   29