Page 25 - DIN Disconnectors
P. 25
25
—
Technical data
—
XLP 3-pole
XLP000 XLP00 XLP1 XLP2 XLP3
For NH fuse links acc. to NH000/NH00C
IEC60269-1/-2/-4 max width = 21 mm NH000/NH00 NH1 NH2 NH3
Rated operational voltage U e AC (V) 400 500 690 400 500 690 800 1000 500 690 800 800 500 690 800 500 690
Rated operational current I e AC (A) 80 100 50 125 160 125 63 125 250 200 160 250 400 315 400 630 500
(A) 100 160 63 125 250 160 250 400 630
Thermal current with fuse link I th
Utilization category AC23B AC22B AC21B AC23B AC22B AC21B AC22B AC22B AC22B AC21B AC22B AC22B AC22B AC21B AC22B AC22B AC21B
Rated insulation voltage U i (V) 690 1000 1000 1000 1000
Rated impulse withstand
voltage U imp (kV) 6 8 8 8 8
Rated conditional short circuit
current (kArms) 50 100 80 50 100 80 50 120** 100 80 50 120* 100 80 120* 100 80
Rated frequency (Hz) 50 - 60 50- 60 50 - 60 50 - 60 50 - 60
Power loss at I th without fuse
link/per phase (W) 1,4 3,5 7,5 13 24
Max allowed poweloss in
the Fuse per phase (W) 7,5 12 23 30 48
Electrical durability 300 200 200 200 200
Mechanical durability 1700 1400 1400 800 800
Degree of protection from the Open IP20 IP20 1) IP20 1) IP20 1) IP20 1)
front acc. to IEC60529
Closed IP30 IP30 1) IP30 1) IP30 1) IP30 1)
Type tested according to EN/IEC 60947-3
* Tested with gS fuse
** Tested with aR fuse
1) For 60 mm Busbar System types IP20/30 can only be achieved with either Cable shroud or Front frame
—
XLP 4-pole
XLP00 XLP1 XLP2 XLP3
For NH fuse links acc. to IEC60269-2-1 NH000/NH00 NH1 NH2 NH3
Rated operational voltage Ue AC (V) 500 500 500 500
Rated operational current Ie (A) 160 250 400 630
Thermal current with fuse-link Ith (A) 160 250 400 630
Utilization category AC22B AC22B AC22B AC22B
Rated insulation voltage U i (V) 1000 1000 1000 1000
Rated impulse withstand voltage U imp (kV) 8 8 8 8
Rated conditional short circuit current (kArms) 50 50 50 50
Rated frequency (Hz) 50 - 60 50 - 60 50 - 60 50 - 60
Power loss (I th) without fuselink,
per phase (W) 3,5 7,5 13 24
Electrical durability 200 200 200 200
Mechanical durability 1400 1400 800 800
Degree of protection from the Open IP20 IP20 IP20 IP20
front acc. to IEC60529 Closed IP30 IP30 IP30 IP30